18
Model
Batteries
(U
cell
x Nº) =
U
nominal
/ U
floating
Minimum features of two
poles protection switch
Voltage
DC (V)
Current (A)
SLC-4000-TWIN PRO
(12V x 20) =
240V / 275V
440
20
SLC-5000-TWIN PRO
25
SLC-6000-TWIN PRO
32
SLC-8000-TWIN PRO
40
SLC-10000-TWIN PRO
50
SLC-8000-TWIN/3 PRO
40
SLC-10000-TWIN/3 PRO
50
SLC-12000-TWIN/3 PRO
(12 V x 24) =
288V / 330V
440
50
SLC-15000-TWIN/3 PRO
63
SLC-20000-TWIN/3 PRO
100
Table 2.
Features of protection between the equipment and battery
cabinet.
• All standard UPSs have batteries in the same enclosure of
the equipment , less those ones as B0 and B1. In the first
ones, the battery protection is done by internal fuses and
there is no access to the end-user.
Accumulator cabinet or modules have battery protection
too, and in this case, they are duplicated. An internal ones
through fuses with no access for the end-user and an addi-
tional ones by means of a two pole circuit breaker.
•
IMPORTANT FOR SAFETY: In case of installing the
batteries by yourself, the accumulators has to be pro-
vided with a two pole circuit breaker protection sized to the
features stated in table 2.
•
Before starting the connection between the bat-
tery module/s and the equipment, check that the
equipment switch/es and the one in the battery cabinet
are in "Off" position.
• Connection terminals with the external batteries are in the
same power block of the equipment, less in TWIN/3 PRO up
to 10 kVA, which have an Anderson connector.
• Connection of the UPS with the battery cabinet will be done by
means of a supplied bundle cables, connecting, at first stage,
one of the ends to the power block or Anderson connector of
the UPS and then the other end to the power block or Anderson
connector of the battery cabinet, by respecting the polarity
stated in the labelling of the equipment and this manual, and
colour of the cables (red for positive, black for negative, green-
yellow for earth).
Battery modules with Anderson connector there is no pos-
sibility to make a mistake in the polarity.
Table 3 states the battery connection type, which are avail-
able in the UPS and battery modules.
• When it is supplied more than one battery unit for each
equipment, the connection will always be done in parallel
between them and the equipment. So it means, black cable
from negative of the UPS to the first negative of the first bat-
tery module and from this last negative to the second module
and so on. Proceed in the same way to connect the red posi-
tive cable and the green-yellow earth cable.
• In parallel systems, the connection of each equipment with
its external battery cabinet/s has to be done like if they were
single units, completely separate from the rest ones.
•
Each battery module is independent for each equip-
ment. It is strictly prohibited to connect two equip-
ments to one battery module.
Model
Battery connection terminals
In the UPS
In the external
battery module
SLC-4000-TWIN PRO
Power block
Anderson connector
SLC-5000-TWIN PRO
SLC-6000-TWIN PRO
SLC-8000-TWIN PRO
Power block
SLC-10000-TWIN PRO
SLC-8000-TWIN/3 PRO
Anderson connector Anderson connector
SLC-10000-TWIN/3 PRO
SLC-12000-TWIN/3 PRO
Power block
Power block
SLC-15000-TWIN/3 PRO
SLC-20000-TWIN/3 PRO
Table 3.
Type of connection terminals in the UPS and battery
module.
5.3.5. Connection of main input earth
terminal
(
)
and the earth bonding
terminal
(
)
.
•
As this is a device with class I protection against electric
shocks, it is essential to install a protective earth conductor
(connect earth (
)). Connect the conductor to the terminal or
bar, before connecting the power supply to the UPS input.
• Make sure that all the loads connected to the UPS are only
connected to the protective earth bonding terminal (
). The
fact of not restricting the earthing of the load or loads and/
or the batteries case/s or cabinet/s to this single point will
create a return loops to earth which will affect the quality of
the supplied power .
• All terminals identified as earth bonding (
), are joined
together, to the main protective earthing terminal (
) and
to the frame of the device.
5.3.6. Terminals for EPO (Emergency
Power Off).
• All UPSs have a terminal strip to install an external button, for
Emergency Power Off (EPO).
• The equipment is preset from factory with the EPO as nor-
mally closed contact (NC). So, the UPS will break the output
power supply when the circuit is open:
Either by removing the female connector inserted in the plinth.
This connector has a cable bridge to close the circuit (Fig. A).
Fig. A
Fig. B
Or by turning on the external button installed and be-
longing to the end-user. The connection in the button has
to be in normally closed because it will open the circuit
when turning it on.
• Through the control panel, it can be selected the reverse
functionality (Password required), normally open (NO).
Less punctual cases, it is not recommended to use this type
USER MANUAL
Summary of Contents for UPS SLC TWIN PRO series
Page 1: ...UNINTERRUPTIBLE POWER SUPPLY USER S MANUAL UPS SLC TWIN PRO series 4 20 kVA...
Page 2: ......
Page 42: ...42 USER MANUAL...
Page 43: ...43 SALICRU...