background image

18

Model

Batteries

(U 

cell

 x Nº) = 

nominal

 / U 

floating

Minimum features of two 

poles protection switch

Voltage

 DC (V)

Current (A)

SLC-4000-TWIN PRO

(12V x 20) =

240V / 275V

440

20

SLC-5000-TWIN PRO

25

SLC-6000-TWIN PRO

32

SLC-8000-TWIN PRO

40

SLC-10000-TWIN PRO

50

SLC-8000-TWIN/3 PRO

40

SLC-10000-TWIN/3 PRO

50

SLC-12000-TWIN/3 PRO

(12 V x 24) = 

288V / 330V

440

50

SLC-15000-TWIN/3 PRO

63

SLC-20000-TWIN/3 PRO

100

Table 2. 

Features of protection between the equipment and battery 

cabinet.

•  All standard UPSs have batteries in the same enclosure of 

the equipment , less those ones as B0 and B1. In the first 

ones, the battery protection is done by internal fuses and 

there is no access to the end-user.
Accumulator cabinet or modules have battery protection 

too, and in this case, they are duplicated. An internal ones 

through fuses with no access for the end-user and an addi-

tional ones by means of a two pole circuit breaker.

• 

IMPORTANT FOR SAFETY: In case of installing the 

batteries by yourself, the accumulators has to be pro-

vided with a two pole circuit breaker protection sized to the 

features stated in table 2.

• 

Before starting the connection between the bat-

tery module/s and the equipment, check that the 

equipment switch/es and the one in the battery cabinet 

are in "Off" position.

•  Connection terminals with the external batteries are in the 

same power block of the equipment, less in TWIN/3 PRO up 

to 10 kVA, which have an Anderson connector.

•  Connection of the UPS with the battery cabinet will be done by 

means of a supplied bundle cables, connecting, at first stage, 

one of the ends to the power block or Anderson connector of 

the UPS and then the other end to the power block or Anderson 

connector of the battery cabinet, by respecting the polarity 

stated in the labelling of the equipment and this manual, and 

colour of the cables (red for positive, black for negative, green-

yellow for earth).
Battery modules with Anderson connector there is no pos-

sibility to make a mistake in the polarity.
Table 3 states the battery connection type, which are avail-

able in the UPS and battery modules.

•  When it is supplied more than one battery unit for each 

equipment, the connection will always be done in parallel 

between them and the equipment. So it means, black cable 

from negative of the UPS to the first negative of the first bat-

tery module and from this last negative to the second module 

and so on. Proceed in the same way to connect the red posi-

tive cable and the green-yellow earth cable.

•  In parallel systems, the connection of each equipment with 

its external battery cabinet/s has to be done like if they were 
single units, completely separate from the rest ones.

• 

Each battery module is independent for each equip-

ment. It is strictly prohibited to connect two equip-

ments to one battery module.

Model

Battery connection terminals

In the UPS

In the external 

battery module

SLC-4000-TWIN PRO

Power block

Anderson connector

SLC-5000-TWIN PRO
SLC-6000-TWIN PRO
SLC-8000-TWIN PRO

Power block

SLC-10000-TWIN PRO
SLC-8000-TWIN/3 PRO

Anderson connector Anderson connector

SLC-10000-TWIN/3 PRO
SLC-12000-TWIN/3 PRO

Power block

Power block

SLC-15000-TWIN/3 PRO
SLC-20000-TWIN/3 PRO

Table 3. 

Type of connection terminals in the UPS and battery 

module.

5.3.5.  Connection of main input earth 

terminal 

(

)

 and the earth bonding 

terminal 

(

)

.

• 

As this is a device with class I protection against electric 

shocks, it is essential to install a protective earth conductor 

(connect earth (

)). Connect the conductor to the terminal or 

bar, before connecting the power supply to the UPS input.

•  Make sure that all the loads connected to the UPS are only 

connected to the protective earth bonding terminal (

). The 

fact of not restricting the earthing of the load or loads and/

or the batteries case/s or cabinet/s to this single point will 

create a return loops to earth which will affect the quality of 

the supplied power .

•  All terminals identified as earth bonding (

), are joined 

together, to the main protective earthing terminal (

) and 

to the frame of the device.

5.3.6.  Terminals for EPO (Emergency 

Power Off).

•  All UPSs have a terminal strip to install an external button, for 

Emergency Power Off (EPO).

•  The equipment is preset from factory with the EPO as nor-

mally closed contact (NC). So, the UPS will break the output 

power supply when the circuit is open: 

 

ˆ

Either by removing the female connector inserted in the plinth. 

This connector has a cable bridge to close the circuit (Fig. A).

 

Fig. A 

Fig. B

 

ˆ

Or by turning on the external button installed and be-

longing to the end-user. The connection in the button has 

to be in normally closed because it will open the circuit 

when turning it on.

•  Through the control panel, it can be selected the reverse 

functionality (Password required), normally open (NO).
Less punctual cases, it is not recommended to use this type 

USER MANUAL

Summary of Contents for UPS SLC TWIN PRO series

Page 1: ...UNINTERRUPTIBLE POWER SUPPLY USER S MANUAL UPS SLC TWIN PRO series 4 20 kVA...

Page 2: ......

Page 3: ...on 5 3 9 Software 5 3 10 Considerations before starting up the connected loads 6 Operating 6 1 Commissioning 6 1 1 Controls before commissioning 6 2 Start up and shutdown of the UPS 6 2 1 Start up of...

Page 4: ...l exclusively Although we have made every effort to guarantee a com plete and accurate information in this user s manual we are not responsible for any errors or omissions that may exist The images in...

Page 5: ...installation and commissioning in an easy and ordered way without doubt Finally once the equipment is installed and operative for future requests or doubts that could arise it is recommended to keep...

Page 6: ...IEC 62040 2 Uninterruptible power supply UPS Part 2 EMC requirements The manufacturers responsibility is excluded in the event of any modification or intervention in the product by the customer s sid...

Page 7: ...due to the constant evolution of the product some discrepancies or small contradictions can arise In front of any doubt the labelling of the equipment will always prevail Figures regarding its main f...

Page 8: ...slot EPO RS 232 USB Protection cover for external batteries IEC output connectors Protection cover for manual bypass switch maintenance and output Protection cover for power blocks USB RS 232 EPO Pro...

Page 9: ...9 SALICRU Battery switch Protection cover for power blocks Batteries module for models 10 kVA Batteries module for models up to 10 kVA Battery switch Power blocks Fig 3 Rear view batteries module...

Page 10: ...ith no accessories screws and electrical cables Batteries owned by the client will be installed out from the case or cabinet of the UPS Under request it is possible to supply the acces sories screws a...

Page 11: ...low input current distortion so mains pollution is decreased Great adaptability to the worst conditions of the input mains Wide margins of the input voltage frequency range and wave shape so it is av...

Page 12: ...adaptor The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of controlling and management at the manager system dis posal This f...

Page 13: ...es type B for RCD devices and C characteristic for circuit breakers For the output load feeding C characteristic for circuit breaker Regarding the size they will be as minimum to the currents stated i...

Page 14: ...o the instructions described in this manual and charge them for 12 hours In parallel systems it is not needed to make the connection among the equipments to charge the batteries It can be treated as s...

Page 15: ...correct torque in the screws of the power blocks In installations with only one UPS the Jumper cable as bridge mode connected from factory between the terminals JP1 and JP2 has to be kept as it is Fo...

Page 16: ...the power contactor 2 with 400V AC coil and NO contact of 5A 1A at least 4 Cable installed from factory as a bridge mode in any TWIN 3 PRO 10 kVA equipment Remove this cable fitted in as a bridge mode...

Page 17: ...connection JP2 Output neutral N Output phase U L Output earth bonding UPS connection power block TWIN PRO UPS connection power block TWIN 3 PRO 10 kVA UPS connection power block TWIN 3 PRO up to 10 k...

Page 18: ...the first bat tery module and from this last negative to the second module and so on Proceed in the same way to connect the red posi tive cable and the green yellow earth cable In parallel systems th...

Page 19: ...and it can t be extended under any other concept due to the risk of interfer ences and communication failures that it could cause In those installations with only one UPS the Jumper cable as bridge mo...

Page 20: ...ion software 5 3 8 2 Smart slot UPS s have a unique slot for TWIN PRO and two slots for TWIN 3 PRO hidden rear the covers stated in the views of the equipment One of them allows inserting the SNMP car...

Page 21: ...h makes a user friendly interface of monitoring and management This software supplies an auto Shutdown for a system based on several PCs in case of an electrical blackout With this soft ware the end u...

Page 22: ...will be done gradually to avoid any problem as minimum in the first commissioning If inductive loads with big inrush current apart from sensi tive ones are required to be connected like laser printers...

Page 23: ...ck that the battery switch is in position On models B0 and B1 Turn the input M1 and bypass M2 circuit breakers to On Switch M2 is only available in models TWIN 3 PRO 10 kVA In equipments with single p...

Page 24: ...sfer to Bypass mode Put all the equipments on manual bypass To do it re move the cover from manual bypass switch which is located at the back of each equipment and turn all the switches to position BY...

Page 25: ...S T S Press over the shutdown key in any UPS for more than 3 seconds and each one will be shutdown supplying output voltage through the bypass Turn On the output circuit breaker switch of the distrib...

Page 26: ...UPS and put the mechanical lock To avoid wrong manoeuvring the mechanical lock has to be fit otherwise the equipment and loads are exposed to serious damages even the de struction of both or fire Turn...

Page 27: ...r 1 sec as minimum to validate the modified option and change the settings Table 6 Functionality of the buttons or keypad of the control panel The UPS has a control panel with the following parts Four...

Page 28: ...s UPS only 8 20 kVA TWIN 3 Blue 81 Fault Heatsink over temperature Red Code Condition Description Color LCD 82 Alarm Ambient over temperature UPS only 4 10 kVA TWIN Blue 83 Alarm Ambient NTC abnormal...

Page 29: ...UPS power supply information single phase input Fig 17 Main screen of the equipment with single phase input Information of load level connected to the UPS UPS power supply information three phase inpu...

Page 30: ...ls due to fault or wrong the equipment will transfer to Battery mode to feed the load s properly Fig 24 Frequency converter mode screen This function can be activated through the settings of the contr...

Page 31: ...beadaptedto the own needs and optimise the function of the equipment 7 3 1 Main screen From main screen when pressing the key or for less than 1 sec it is shown detailed information about the alarm pa...

Page 32: ...UPS status menu Structure of main menu Press 1 sec Fig 31 UPS status screen Press 1 sec Press o 1 sec Structure of Data logger submenu Structure of main menu Press 1 sec Fig 32 Event logger submenu Pr...

Page 33: ...T S password only Fig 34 Control submenu screens 7 3 5 Control submenu When pressing the key the key for less than 1 sec from this Control submenu it is accessed to the control structure see figure 34...

Page 34: ...ation from factory 7 4 1 Operating on ECO mode 7 4 1 1 Short description of the ECO mode ECO mode function allows supplying the load s from mains directly through the internal filters only meanwhile t...

Page 35: ...rs or service cen tres in order to avoid overheating and sparks with fire risk because the size is not enough Do not short the and poles of the batteries there is risk of fire or electrocution Be sure...

Page 36: ...ooling and the ambient temperature of the room NTC abnormal UPS internal fault Consult with the S T S Communication cable male disconnected Para cable Male Loss Alarm code E3 Parallel bus cable is dis...

Page 37: ...er Under Voltage Inv Under Voltage Alarm code 33 UPS internal fault Consult with the S T S Inverter Softstart Failed Inv Softstart Fail Alarm code E34 UPS internal fault Consult with the S T S Negativ...

Page 38: ...ypothetical fault 8 3 2 Out of scope of supply Our company is not forced by the warranty if it appreciates that the defect in the product doesn t exist or it was caused by a wrong use negligence insta...

Page 39: ...oad 2 Voltage THD with non linear load 5 Output voltage recovering time 100 ms IEC 62040 3 70 ms IEC 62040 3 60 ms IEC 62040 3 Transient response of the output voltage with load fluctuation of 0 100 0...

Page 40: ...ending on model 273 V DC 13 65 V DC block 4 A 345 6 V DC 14 4 V DC block Floating voltage block set 13 65 V DC 273 V DC 13 65 V DC 327 6 V DC Maximum charging current 1 A 1 4 A 4 A Recharging time 5 h...

Page 41: ...mitting Diode Circuit breaker A circuit breaker or switch is a device ready to break the electrical current of a circuit when it over comes the maximum set values On Line mode Regarding to an equipmen...

Page 42: ...42 USER MANUAL...

Page 43: ...43 SALICRU...

Page 44: ...mpany salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Se...

Reviews: