27
SALICRU
7. Control panel with
LCD.
7.1. Control panel.
Fig. 16.
Control panel view.
Button
Function
Description
Inverter start up
With no AC power supply and battery connected
to the equipment (B0 or B1 equipments), press
the button for 1 sec. as minimum to start up the
inverter.
UPS start up
When the unit is supplied from the AC input
voltage and it is on bypass mode, press the key
for more than 1 sec. to start up the inverter.
UPS shutdown
When the equipment is ON and it has to be
shutdown, presss for more than 3 sec. over this
key.
Enter into the
main menu
When showing the main screen of the UPS
by default in the LCD, press over this key for
more than 1 sec. to enter into the main menu
structure.
Exit from main
menu
Press over this key for more than 1 sec. to
escape from the current menu, to the menu
by default in the UPS, without executing any
command or changing any configuration.
Move upwards
Press this key for 1 sec. as minimum to move
up in the browsing inside a menu.
Move downwards
Press this key for 1 sec. as minimum to move
down in the browsing inside a menu.
Enter into the
structure of the
next menu
Press this key for 1 sec. as minimum to select
the option in the current menu or to enter in the
next menu, but without changing any setting.
Select an option
of the menu
Press the key for 1 sec. as minimum to select
the option in the current menu or to enter in the
next menu, but without changing any setting.
Validate the
current setting
Press the key for 1 sec. as minimum to validate
the modified option and change the settings.
Table 6.
Functionality of the buttons or keypad of the control panel.
• The UPS has a control panel with the following parts:
Four buttons or membrane keys, see table 6.
A LCD panel with two colours backlight. By default, the
text or graphics messages are shown in white colour over
blue background.
When a critical alarm is activated on the UPS, the light of
the text or graphic changes to dark orange with orange
background.
Four led optical indicators that provides the following in-
formation:
–
Normal (green).
–
Battery (yellow).
–
Bypass (yellow).
–
Fault (red).
Table 7 shows the individual function of each one of them
or the interaction among them, as regards to the UPS
status.
7.1.1. Functionality of the LEDs.
UPS status
Leds
Normal
Battery
Bypass
Fault
Bypass mode without output
Bypass mode with output
UPS start up
Line mode
Battery mode
ECO mode
Battery test mode
Failure mode
Warning
: Permanently light.
: Sequential and rotative light.
: Blinking light.
: It depends on the fault, warning or any other condition.
Table 7.
Function of the led optical indications.
7.1.2. Acoustic alarms.
Alarm condition
Modulation or alarm tone
Active fault
Continuous
Active warning
Beep every second
Output from battery
Beep every 4 seconds. With low battery (end
of back up time), one beep every second.
Output from bypass
Beep every 2 seconds
Table 8.
Acoustic alarms. Condition and modulation or tone.
7.1.3. UPS status and color LCD display,
as condition.
Code
Condition
Description
Color LCD
01
State
Bypass abnormal.
Blue
02
State
Utility abnormal.
Blue
03
State
HE abnormal.
Blue
04
Warning
Site wiring fault (UPS only 4.. 10 kVA
TWIN).
Blue