8.2.1. Troubleshooting guide. Warning
indications.
Indication in the LCD
Possible cause
Solution
TWIN PRO 4-10 kVA TWIN/3 PRO 8-20 kVA
Read EEPROM Error
-
UPS internal fault
Consult with the S.T.S.
Emergency Power Off EPO Active
Alarm code:71
EPO connector is open
Check the status of the EPO connector
On Maintain Bypass
On Maintain Bypass
Alarm code:72
Manual bypass switch on BYPASS position
and/or switch protection cover removed
Check the position of the switch and/or the location of the protection
cover
Site Wiring Fault
-
Phase and neutral wires from input and
output are reversed
Swap the phase and neutral connection
Battery Disconnected Battery Disconnect
Alarm code:11
Battery set is not properly connected
Battery test to be confirmed
Check that the battery cabinet is connected (models (B0) and (B1))
Check the battery switch is on "On" position
Low Battery Warning
Battery low
Alarm code:12
Low battery voltage
When the alarm beeps every 1 sec., means end of back up time
Output Overload
Output Overload
Alarm code:41
Output overload
Check the load and remove the non-critical ones
Check if any load is faulty or damaged
Fan Failure
Fan Failure
Alarm code:84
Faulty fan/s
Check that the fan/s are working properly
Charger Failure
Charger Fail
Alarm code:15
Battery charging fault
Consult with the S.T.S.
Battery DC Over
Voltage
-
Battery voltage is higher than the normal
Check if the battery quantity is the suitable one
Over Charge
Over Charge
Alarm code:14
Battery overcharged
The UPS transfers to "Battery mode" automatically and later on it
checks if the battery voltage and mains are OK (corrects), the UPS
returns back to "Normal mode" automatically again
Model Pin Error
Model Pin Error
Alarm code:92
UPS internal fault
Consult with the S.T.S.
Ambient Over
Temperature
-
Ambient temperature is too high
Check the ambient cooling
Heatsink Over
Temperature Warning
Heatsink Over
Temperature
Alarm code:86
The temperature inside the equipment is
too high
Check the UPS cooling and the ambient temperature of the room
NTC abnormal
-
UPS internal fault
Consult with the S.T.S.
Communication cable
male disconnected
Para cable Male Loss
Alarm code:E3
Parallel bus cable is disconnected
Check the parallel bus cable
Communication cable
female disconnected
Para cable Female
Loss
Alarm code:E4
Parallel bus cable is disconnected
Check the parallel bus cable
Parallel Battery
Connection Different
Para Bat Differ
Alarm code:E6
The battery set is disconnected from the
UPS
Check that all battery modules are connected
Parallel input Different
-
Any UPS input is disconnected
Check the connection of the room and building and the input connection
Make sure that the input switch is turned "On"
Check that all UPSs are connected to the same mains power supply
-
Para Byp Differ
Alarm code:E8
Switch (M2) from bypass line of any
equipment is disconnected (this switch is not
available in models TWIN/3 PRO 8-10 kVA)
Check the connection of the room and building and the input connection
Make sure that the bypass switch (M2) is turned "On"
Check that all UPSs are connected to the same mains power supply
-
Para Line Differ
Alarm code:E7
Switch (M1) from input line of any equipment
is disconnected
Check the connection of the room and building and the input connection
Make sure that the input switch (M1) is turned "On"
Check that all UPSs are connected to the same mains power supply
Parallel Power
strategy setting
different
Para Work Mode
Differ
Alarm code:E9
There are different structure configurations
set in the parallel system
The UPSs with different configuration do not accept the paralleling (i.e.:
one on line mode and the other one on converter mode)
Parallel rated power
capacity setting
different
Para Rate Differ
Alarm code:EA
There are different UPSs in the parallel
system
Equipments with different power rate do not accept the parallel (i.e.: one
of 8 kVA and another one of 10 kVA)
Parallel in HE mode
ECO In Para
Alarm code:EB
ECO function is activated in the parallel
system
ECO function is not allowed in a parallel system
Parallel load
unbalance
-
UPS internal fault
Consult with the S.T.S.
Table 10.
Troubleshooting guide. Warning indications.