8.2.2. Troubleshooting guide. Fault
indications.
Indication in the LCD
Possible cause
Solution
TWIN PRO4-10 kVA TWIN/3 PRO 8-20 kVA
Inverter Overload
Fault
Inverter Overload
Fault
Alarm code:42
Overload
Check the load and remove the non-critical ones
Check if any load is faulty or damaged
Bypass Overload
Fault
Byp Overload Fault
Alarm code:43
Overload
Check the load and remove the non-critical ones
Check if any load is faulty or damaged
Output Short Circuit
Output Short Circuit
Alarm code:31
Output shortcircuit
Disconnect all the loads. Shutdown the UPS. Check if the UPS output
and loads are on short-circuit. Make sure that the short-circuit has
been removed before starting up the UPS and loads
Heatsink Over
Temperature Fault
-
The temperature inside the equipment is
too high
Check the UPS cooling and the ambient temperature of the room
-
Heatsink Over
Temperature Fault
Alarm code:81
The temperature inside the equipment is
too high
Make sure that the UPS is not overloaded, cooling holes are not
blocked and the ambient temperature is not too high.
Shutdown the equipment and leave it at rest for 10 minutes as
minimum to decrease the temperature before starting it up again. If the
fault happens again, contact with the S.T.S.
Bus Over Voltage
Bus Over Voltage
Alarm code:21
UPS internal fault
Consult with the S.T.S.
Bus Under Voltage
Bus Under Voltage
Alarm code:22
UPS internal fault
Consult with the S.T.S.
Bus Unbalance
Bus Unbalance
Alarm code:23
UPS internal fault
Consult with the S.T.S.
Bus short
Bus short
Alarm code:24
UPS internal fault
Consult with the S.T.S.
Bus Softstart Failed
Bus Softstart Fail
Alarm code:25
UPS internal fault
Consult with the S.T.S.
Inverter Over Voltage Inv Over Voltage
Alarm code:32
UPS internal fault
Consult with the S.T.S.
Inverter Under
Voltage
Inv Under Voltage
Alarm code:33
UPS internal fault
Consult with the S.T.S.
Inverter Softstart
Failed
Inv Softstart Fail
Alarm code:E34
UPS internal fault
Consult with the S.T.S.
Negative Power Fault Negative Power Fault
Alarm code:E1
Load is completely inductive or capacitive
Shutdown some non-critical loads.
The inrush current of the loads is done through the Bypass. Make sure
that there is not an overload and proceed with the start up of the UPS
Fatal EEPROM Fault
-
UPS internal fault
Consult with the S.T.S.
Cable male and
female disconnected
fault
Cable male and
female Loss fault
Alarm code:E2
Parallel bus cable is disconnected
Check the parallel bus cable
-
Backfeeder
Alarm code:93
UPS internal fault
Do not touch the terminals of the equipment, which is connected
to an electrical installation with a UPS. Even without the electrical
power supply is very dangerous, because the equipment is an energy
generator. Consult with the S.T.S.
Table 11.
Troubleshooting guide. Fault indications.
8.2.3. Troubleshooting guide. Other
circumstances.
Problem
Possible cause
Solution
No indications and no warning alarms,
although the UPS is connected in the
electrical mains
There is not input voltage
Check the building wiring and UPS power cord. Check UPS input
switch and protection panel are turned "On"
BYPASS led lights although there is power
supply
The inverter doesn't start up
Press over the start up key for more than 1 second, the acoustic
alarm will beep for 1 sec. and the UPS is turned "On"
BATTERY led lights and the acoustic alarm is
triggered (1 beep every 4 sec.)
Input voltage and/or frequency out of range
Check the power supply. Check wiring of the building and the power
supply cable of the UPS. Make sure that the UPS input switch and the
protection panel are turned "On"
Back up time is shorter than the nominal
Batteries are not fully charged
Faulty batteries
Charge the batteries for 12 hours and check the capacity
Table 12.
Troubleshooting guide. Other circumstances.