Installation and operating instructions Ixens, Ixens Bloc
105
5.1.0.0
Multi pump
Double pump
Only displayed when DP is
active (incl. sub-menus)
5.1.1.0
Operating mode
Main/standby operation
Only displayed for double
pump master
Parallel operation
Only displayed for double
pump master
5.1.2.0
Setting, MA/SL
Manual converting from master
to slave mode
Only displayed for double
pump master
5.1.3.0
Pump cycling
Only displayed for double
pump master
5.1.3.1 Manual pump
cycling
Carries out pump cycling inde-
pendent of the countdown
Only displayed for double
pump master
5.1.3.2 Internal/external
Internal pump cycling
Only displayed for double
pump master
External pump cycling
Only displayed for double
pump master, see “AUX” ter-
minal
5.1.3.3 Internal: Time
interval
Can be set between 8 h and 36 h
in 4 h steps
Displayed when internal
pump cycling is activated
5.1.4.0
Pump enabled/
disabled
Pump enabled
Pump disabled
5.1.5.0
SSM
Individual fault signal
Only displayed for double
pump master
Collective fault signal
Only displayed for double
pump master
5.1.6.0
SBM
Individual readiness signal
Is only displayed for double
pump master and SBM func-
tion at readiness/operation
Individual run signal
Only displayed for double
pump master
Collective readiness signal
Only displayed for double
pump master
Collective run signal
Only displayed for double
pump master
5.1.7.0
External off
Individual external off
Only displayed for double
pump master
Collective external off
Only displayed for double
pump master
5.2.0.0
BMS
Settings for Building Manage-
ment System (BMS) – building
automation
Incl. all sub-menus, only dis-
played when BMS is active
5.2.1.0
LON/CAN/
IF-Module
Wink/service
The wink function permits the
identification of a device in the
BMS network. A “wink” is exe-
cuted by confirmation.
Only displayed when LON,
CAN or IF-Module is active
5.2.2.0
Local/remote
operation
BMS local operation
Temporary state, automatic
reset to remote operation
after 5 min
BMS remote operation
No.
Designation
Type
Symbol Values/explanations
Display conditions
±
±
±
±
±
±
±
±
±
±
±
Summary of Contents for IXENS
Page 2: ......
Page 3: ......
Page 8: ...Fig 7 Ixens 13 20 22 21 15 16 17 18 19 14 13 12 11 10 9 8 7 4 3 2 1 6 5 20b 20a ...
Page 75: ...Français Notice de montage et de mise en service Ixens Ixens Bloc 67 ...
Page 137: ...English Installation and operating instructions Ixens Ixens Bloc 129 ...
Page 203: ...Italiano Istruzioni di montaggio uso e manutenzione Ixens Ixens Bloc 195 ...
Page 335: ......