English
120
Salmson 05/2015
11.2
Error table
Classi-
fication
No.
Fault
Cause
Remedy
Error type
HV
AC
-
0
No fault
System
errors
E004
Undervoltage
Mains overloaded
Check electrical installation
C
A
E005
Overvoltage
Mains voltage too high
Check electrical installation
C
A
E006
2-phase operation
Missing phase
Check electrical installation
C
A
E007
Warning!
Generator
operation
(flow in flow direction)
The flow is driving the
pump impeller; electrical
current is being fed back
to the mains
Check the setting, check sys-
tem for proper operation
Caution!
Prolonged operation
can cause damage to the elec-
tronic module
F
F
E009
Warning!
Turbine
operation (flow in flow
direction)
The flow is driving the
pump impeller; electrical
current is being fed back
to the mains
Check the setting, check sys-
tem for proper operation
Caution!
Prolonged operation
can cause damage to the elec-
tronic module
F
F
Pump errors
E010
Blocking
Shaft is mechanically
blocked
If the blocking has not been
removed after 10 seconds, the
pump switches off.
Check shaft for ease of move-
ment
Request customer service
A
A
Motor errors
E020
Excess winding tem-
perature
Motor overloaded
Allow motor to cool down
Check settings
Check/correct the duty point
B
A
Motor ventilation limited Provide unobstructed air
access
Water temperature too
high
Lower water temperature
E021
Motor overload
Duty point outside of
duty chart
Check/correct the duty point
B
A
Deposits in the pump
Request customer service
E023
Short circuit/earth
leakage
Motor or electronic mod-
ule defective
Request customer service
A
A
E025
Faulty contact
Electronic module has no
contact to motor
Request customer service
A
A
Winding interrupted
Motor faulty
Request customer service
E026
WSK or PTC inter-
rupted
Motor faulty
Request customer service
B
A
Electronic
modules
errors
E030
Excess electronic
module temperature
Limited air supply to the
heat sink of the elec-
tronic module
Provide unobstructed air
access
B
A
E031
Excess hybrid/power
section temperature
Ambient temperature too
high
Improve room ventilation
B
A
E032
Intermediate circuit
undervoltage
Voltage fluctuations in
the mains
Check electrical installation
F
D
E033
Intermediate circuit
overvoltage
Voltage fluctuations in
the mains
Check electrical installation
F
D
E035
DP/MP: multiple
instances of same
identity
Multiple instances of
same identity
Reallocate master and/or slave
(see Chapter 9.2 on page 109)
E
E
Summary of Contents for IXENS
Page 2: ......
Page 3: ......
Page 8: ...Fig 7 Ixens 13 20 22 21 15 16 17 18 19 14 13 12 11 10 9 8 7 4 3 2 1 6 5 20b 20a ...
Page 75: ...Français Notice de montage et de mise en service Ixens Ixens Bloc 67 ...
Page 137: ...English Installation and operating instructions Ixens Ixens Bloc 129 ...
Page 203: ...Italiano Istruzioni di montaggio uso e manutenzione Ixens Ixens Bloc 195 ...
Page 335: ......