Commissioning
Safety
DANGER! Risk of fatal injury!
Failure to install safety devices of the electronic module and the
motor can cause electrical shock or contact with rotating parts,
potentially resulting in life-threatening injuries.
• Before commissioning as well as after maintenance work, all safety
devices such as
module covers and fan cover that were removed
must be reinstalled.
• Keep a safe distance during commissioning.
• Never connect the pump without the electronic module.
Preparation
Before commissioning, the pump and electronic module must be at
the ambient temperature.
9.1
Filling and venting
• Prime and vent the unit correctly.
CAUTION! Risk of property damage!
Running dry will destroy the mechanical seal.
• Make sure that the pump does not run dry.
• To avoid cavitation noises and damage, a minimum inlet pressure
must be guaranteed at the suction port of the pump. This minimum
inlet pressure depends on the operation situation and the duty point
of the pump, and must be defined accordingly.
• The main parameters for defining the minimum inlet pressure are the
NPSH of the pump at its duty point and the vapour pressure of the fluid.
5.8.1.3 Pump kick speed
Can be set between the pump's
minimum and maximum speeds
Is not displayed if pump kick
is deactivated
6.0.0.0
Error acknowl-
edgement
For additional information, see
chapter 11.3 “Acknowledge
fault” on page 122.
Only displayed if an error is
present
7.0.0.0
Access disable
“Access disable” inactive
(changes possible)
(for further information, see
chapter 8.6.7 “Activating/deac-
tivating access disable” on
page 101).
“Access disable” active (no
changes possible)
(for further information, see
chapter 8.6.7 “Activating/deac-
tivating access disable” on
page 101).
No.
Designation
Type
Symbol Values/explanations
Display conditions
±
±
±
Summary of Contents for IXENS
Page 2: ......
Page 3: ......
Page 8: ...Fig 7 Ixens 13 20 22 21 15 16 17 18 19 14 13 12 11 10 9 8 7 4 3 2 1 6 5 20b 20a ...
Page 75: ...Français Notice de montage et de mise en service Ixens Ixens Bloc 67 ...
Page 137: ...English Installation and operating instructions Ixens Ixens Bloc 129 ...
Page 203: ...Italiano Istruzioni di montaggio uso e manutenzione Ixens Ixens Bloc 195 ...
Page 335: ......