5.7 Advanced programming

MAXIMUM    CURRENT

AUT.              16.5 A

MAXIMUM    CURRENT

MAN.           16.5 A

IT IS USED TO SET THE

OVERLOAD MAXIMUM CURRENT

OF THE MOTOR 

RANGE 0.5 ÷ 36.0A  (SA687.xx)

CURRENT    DELAY

4 s

CURRENT     DELAY

4 s

IT IS USED TO SET THE DELAY

OF THE INTERVENTION FOR THE

PROTECTION OF THE CURRENT

RANGE 1 ÷ 8s

AUT. 

INDICATES THAT THE MAXIMUM 

CURRENT VALUE HAS BEEN SET WITH 

THE AUTO-LEARNING 

MAN. 

INDICATES THAT THE

MAXIMUM CURRENT VALUE

HAS BEEN SET MANUALLY

RANGE 0.5 ÷ 18.0A  (SA684.xx)

MINIMUM     CURRENT

AUT.              9.9 A

MINIMUM    CURRENT

MAN.           9.9 A

RANGE 0.5 ÷ 33.0A  (SA687.xx)

RANGE 0.5 ÷ 15.0A  (SA684.xx)

IT IS USED TO SET THE

MINIMUM CURRENT

OF THE MOTOR

MAN.

INDICATES THAT THE

MINIMUM CURRENT VALUE

HAS BEEN SET MANUALLY

MINIMUM    CURRENT

OFF

AUT.

 INDICATES THAT THE MINIMUM 

CURRENT VALUE HAS BEEN SET

WITH THE AUTO-LEARNING,

EXCLUDING THE COS

φ

  APPLICATION

5.1

5. PROGRAMMING

OFF 

EXCLUDES THE CONTROL

ON THE MINIMUM CURRENT

 

33

OFF

 EXCLUDES THE MAX

STARTS CONTROL

IT IS USED TO SET THE MAXIMUM

NUMBER OF STARTS PER HOUR

MAX    STARTS    PER

HOUR                   OFF

MAX    STARTS    PER

HOUR                   OFF

MAX    STARTS    PER

HOUR              10

MINIMUM    CURRENT

RESET                  OFF

OFF

 EXCLUDES THE

MINIMUM CURRENT RESET

IT IS USED TO SET THE

RESET TIME ON THE

MINIMUM CURRENT

RANGE 1min ÷ 99h 59min

MINIMUM     CURRENT

RESET            OFF

MINIMUM     CURRENT

RESET             0 h        5 m

N.B.: 

ABSENT ON

COS  APPLICATION

φ

RANGE 1 ÷ 30

MOTOR   TEST

OFF

MOTOR   TEST

48h

MOTOR   TEST

OFF

OFF 

EXCLUDES THE 

MOTOR TEST 

IT IS USED TO SET THE

DELAY BETWEEN EACH

ACTIVATION OF THE MOTOR TEST

RANGE 0FF - 24 - 48 - 72 - 96h

Summary of Contents for MULTIPLUS 1 SA684 Series

Page 1: ...N AND INSTALLATION MANUAL Direct starting electronic control panel 1 motor for clean water and sewage with display and general disconnecting switch with door lock rev 6 11 01 2023 MULTIPLUS 1 SA684 xx...

Page 2: ...programming 6 General functioning of the control panel 6 1 General functioning 6 2 Application cos 6 3 Application clean water 6 4 Application sewage 6 5 Application 4 20mA bar 6 6 Application 4 20mA...

Page 3: ...t If necessary substitute the various components only with those having the same characteristics and components as the originals 1 GENERAL INSTRUCTIONS FOR INSTALLING 2 WARNINGS ELECTRIC SHOCKS Risk o...

Page 4: ...Float switch for clean water Level probe 1 INPUT 2 INPUTS KLIX1 COM COM MIN MAX KLIX1 G MIN COM 2 START STOP COM MIN MAX CLEAN WATER DRY RUNNING COS KLIX1 COM MIN MAX G MAX2 G ALAR COM COM COM MIN MI...

Page 5: ...tive probe 4 20mA Below are some practical examples of applications that can be implemented with the MULTIPLUS 1 control panel 4 20mA bar 5 STOP START KLIX1 KLIX1 G MIN G MAX1 G ALAR G ALAR COM COM AL...

Page 6: ...2 5 mm M3 0 5Nm 8 3 mm PIEZORESISTIVE LEVEL TRANSMITTER 4 20mA WIRING PRESSURE TRANSDUCER WIRING BROWN WHITE KEY 1 2 LEVEL PROBES OR MINIMUM FLOAT SWITCH 3 4 LEVEL PROBES OR MAX1 FLOAT SWITCH 5 6 MAX...

Page 7: ...0 5Nm 8 3 mm L1 L2 L3 U V W M 3 MOTOR POWER SUPPLY 400 Vac 50 60 Hz 4 2 Wiring diagram SA687 xx 4 WIRING DIAGRAMS KEY 3 4 LEVEL PROBES OR MAX1 FLOAT SWITCH 1 2 LEVEL PROBES OR MINIMUM FLOAT SWITCH 9 1...

Page 8: ...oll forward through the setup pages It is used to increase the value of a parameter It is used to scroll back through the setup pages It is used to reduce the value of a parameter Pressed it allows to...

Page 9: ...AND G MAX OPEN ENABLE MOTOR EXTERNAL COMMAND OFF IN OFF MODE THE MOTHERBOARD EXCLUDES THE CONTROL ON THE EXTERNAL COMMAND 5 1 5 PROGRAMMING 29 THE MOTHERBOARD AUTOMATICALLY CALCULATES THE WAITING FILL...

Page 10: ...CHAPTER 5 7 BY PRESSING IT YOU RETURN TO THE FIRST SETUP SCREEN SEE CHAPTER 5 7 PRESSING IT FOR MORE THAN 1s YOU GO OUT OF THE SETUP AND THE PARAMETERS ARE STORED IN THE MEMORY PRESSING IT FOR MORE T...

Page 11: ...MUM PRESSURE OFF MINIMUM PRESSURE OFF IT IS USED TO SET THE REQUIRED PRESSURE BELOW WHICH THE MOTOR STOPPED AT THE MOTOR STARTING THIS PARAMETER IS BYPASSED FOR 1 MINUTE MINIMUM PRESSURE 0 5bar OFF EX...

Page 12: ...EVEL 1 00 m RANGE 0 10 24 95m ALARM LEVEL 1 00m ALARM LEVEL 1 00m IT IS USED TO SET THE WATER LEVEL ABOVE WHICH THE MOTHERBOARD ENABLES THE ALARM OUTPUT RANGE 1 0 25 0m RANGE 0 05 24 9m IT IS USED TO...

Page 13: ...DICATES THAT THE MINIMUM CURRENT VALUE HAS BEEN SET MANUALLY MINIMUM CURRENT OFF AUT INDICATES THAT THE MINIMUM CURRENT VALUE HAS BEEN SET WITH THE AUTO LEARNING EXCLUDING THE COS APPLICATION 5 1 5 PR...

Page 14: ...VOLTAGE BY PRESSING IT YOU RETURN TO THE FIRST SETUP SCREEN SEE CHAPTER 5 1 5 PROGRAMMING 34 PRESSING IT FOR MORE THAN 1s YOU GO OUT OF THE SETUP AND THE PARAMETERS ARE STORED IN THE MEMORY OFF EXCLU...

Page 15: ...LAYS MEASURED VOLTAGE ABSORBED CURRENT COS DETECTED OPERATING HOURS OF THE MOTOR AUTOMATIC MOTOR Cf 0 80 13 2A STOP MOTOR Cf 1 00 0 0A 400V 13 2A Cf 0 80 0h IT IS USED TO START THE MOTOR MANUALLY EXTE...

Page 16: ...ON G MAX1 CLOSED ALL OFF G ALAR OPEN ON G ALAR CLOSED 17 6 1 6 1 ONLY IN STABLE MANUAL BUTTON MODE EXTERNAL COMMAND OFF IF THE MOTHERBOARD DETECTS A DRY RUNNING CONDITION IT WILL BE POSSIBLE TO DISPL...

Page 17: ...BLE MANUAL BUTTON MODE THE FOLLOWING SCREEN DISPLAYS MEASURED VOLTAGE ABSORBED CURRENT SYSTEM PRESSURE OPERATING HOURS OF THE MOTOR IT IS USED TO START THE MOTOR MANUALLY THIS SCREEN IS DISPLAYED WHEN...

Page 18: ...0h MOT MAINTENANCE SET OFF MOT MAINTENANCE SET OFF MOT MAINTENANCE ENTER TO RESET LAST MOTOR MAINTENAN 0h LAST MOTOR MAINTENAN 500h SCREEN DESCRIPTION PERFORM MOTOR MAINTEN Exceeded the set time this...

Page 19: ...rated 8 2 Event data logger SETUP PREMI PAGE MAN 10s ON EV 12 MIN CURR MAN 8 2A 30h EV 10 MAX VOLT OFF 10h Maximum voltage Maximum motor starts per hour Minimum current The event data logger is used t...

Page 20: ...0 MAXIMUM CURRENT alarm Maximum current set on the setup less than that absorbed by the motor Motor blocked or damaged Application 4 20mA meters The displayed level in meter is wrong Clean carefully...

Page 21: ...llowing message If the voltage is within the set range and stays there for 60 seconds the motherboard will automatically reset the alarm If the motherboard detects the absence of one of the three phas...

Page 22: ...do il riciclaggio di questo prodotto contattate per cortesia il Vs ufficio locale il Vs servizio di smaltimento rifiuti domestici o il negozio dove avete acquistato questo prodotto Questo simbolo sul...

Page 23: ...i responsabilit per danni cagionati da caduta uso scorretto alterazione o negligenza 4 Questa garanzia non incide sui diritti del consumatore sanciti dalla normativa vigente Salupo S r l Salupo S r l...

Page 24: ......

Reviews: