67
dXX
Function
Parameter
Values
Description
Default
Values
d04
Internal relay
(active when d03=1)
0
The controller measures the temperature only at the external sensor
0
1
The sensor is used as a protection against overheating of the floor
d05 (only
in UFH)
Control of the cooling mode
1
SPAN ±0.5°C
2
2
SPAN ±1.0°C
d06 (only
with TRV)
TRV control algorithm
0
Standard ON/OFF algorithm
1
1
Automatic selection
2
Advanced self-learning algorithm
d07
Valve protection
0
Disable
1
1
Enable
d08
Frost protection temperature
5-17°C
Frost protection temperature (and for holiday mode)
5°C
d09
Time format
0
12 hours
1
1
24 hours
d11
Summer time change
0
Disabled
1
1
Enabled
d12
Heating temperature limit
5-35°C
Maximum heating/cooling temperature that can be set by the user
35°C
d13
Cooling temperature limit
5-40°C
Minimum heating/cooling temperature that can be set by the user
5°C
d14
Max floor temperature
(active in heating mode when
d04=1)
6-45°C
To protect the floor against overheating, the heating will be switched off when
the maximum temperature of the floor sensor is reached.
27°C
d15
Min floor temperature
(active in heating mode when
d04=1)
6-45°C
To protect the floor, heating will be activated when the minimum floor sensor
temperature has been reached.
10°C
d16
Lower floor temperature limit
for cooling (Function active
when d04 = 1).
6-45°C
To protect the floor, cooling will be switched off when the set minimum
temperature is reached.
6°C
FEATURES AVAILABLE ONLY FROM THE APPLICATION LEVEL:
d17
Allow buttons to be unlocked
from the thermostat
0
OFF
1
1
ON
d18
Deactivate the need to
confirm the change of the
temperature setpoint by
pressing the
button.
0
OFF
0
1
ON