Fig. 6.1 Controller option setting/checking 

a) option preset checking 

b) option preset setting 

Settings  of  each  controller  option  are 

described below. 

6.1.

 

Setting of deltas 



14 

The 

controller 

allows 

to 

set 

temperature difference 

dT=T1-T2

 that 

will start the collector pump.  

Possible  setting  values  are: 

4,  6, 

8, 10, 12, 14K

.  

6.2.

 

Critical  temperature  alarm 

AL 

Critical  temperature  is  such  collector 
temperature  (T1  sensor)  that  despite 

collector  pump  stopping,  after  reaching  reservoir 
temperature  preset,  will  start  collector  pump  in 
order  to  discharge  excessive  heat  from  the 
collector.  

The  controller  allows  you  to  turn  on  or  off 

loud alarm for the collector critical temperature. If 

AL

  option  is  off,  the  controller  will  not  sound 

audible  alarm  when  the  critical  temperature  is 
reached,  but  it  will  take  alarm  action  (discharge 
heat from the collector into the reservoir). 

6.3.

 

Maximal 

DHW 

temperature 

Max85÷95 

The  controller  allows  you  to  set 
maximal temperature for the reservoir. 
It  is  T2  temperature  above  which  the 

controller  will  start  the  reservoir  overheating 
alarm  and  it  will  stop  heat  loading  to  the 
reservoir. 

This alarm has the highest priority and it will 

always  stop  the  collector  pump  operation.  It 
means  that  even  in  case  of  critical  collector 
temperature, the reservoir overheating alarm will 
disable the collector pump from further operation. 
 

It  possible  to  set  three  values  for  the 

reservoir  maximal  temperature  option:  85,  90, 
95°C 

7.

 

CONTROLLER 

OPERATING 

ALGORITHM 

When 

switched 

on 

the 

controller 

automatically starts to control the collector pump 
operation. 

When  the  T1  sensor  temperature  reaches 

minimal  collector  operation  value  (TCOLmin),  the 
controller  will  enable  the  collector  pump 
operation. Such status is indicated by illumination 
of  the  sun  symbol  indicator.  When  the  collector 
temperature  drops  two  degrees  below  minimal 
temperature  preset,  the  sun  symbol  will  go  off 
and the controller will disable the collector pump, 
if the last was working.  

 

The 

collector 

minimal 

temperature  

TDHWmin is set by selecting edition at the 
sun symbol indicator 

If  the  temperature  difference  between  the 

collector  and  reservoir  (T1-T2)  exceeds  value  set 
in  options  as  d4÷14  and  the  minimal  collector 
temperature  is  reached  (sun  indicator  is  lit),  the 
controller  will  start  the  collector  pump  and  it  will 
be loading heat into the reservoir (sun indicator is 
lit)  until  the  temperature  difference  T1-T2<dT-2 
(current dT is lower than preset by two degrees) 
or  the  collector  temperature  (T1  sensor)  drops 
below  minimal  collector  temperature  (TCOLmin-
2). Then, the collector pump will be turned off.  

The controller turns the collector pump off 

and  on  in  cycles,  depending  on  sunlight intensity 
and  reservoir  conditions,  by  the  time  when  the 
DHW  reservoir  preset  temperature  (TsDHW)  is 
reached.  

 

The  reservoir  preset  temperature  TsDHW  
is  set  by  selecting  edition  at  the  T2 
indicator 

When 

the 

DHW 

reservoir 

preset 

temperature  is  reached,  the  controller  will  stop 
the 

collector 

pump, 

until 

the 

reservoir 

temperature (T2 sensor) is lower than the preset 
by  one  degree  (T2<TsDHW-1).  Then,  the 
controller  will  restart  the  collector  pump,  if 
current conditions allow the reservoir loading. 

When  the  collector  pump  is  stopped, 

because  the  reservoir  preset  temperature  has 
been  reached,  the  controller  will  monitor  the 
collector  temperature  (T1  sensor)  and  if  it 
exceeds  preset  value  TCOLcr,  the  controller  will 
start  the  collector  pump  to  discharge  the 
collector’s critical temperature. When the collector 
temperature drops in relation to TCOLcr preset by 
2°C, the controller will stop to force its operation.  

 

The  collector  critical  temperature  TCOLcr  
is  set  by  selecting  edition  at  the  T1 
indicator 

 

Summary of Contents for PCSol 150

Page 1: ...Controller PCSol 150 REVISION 1 1 SOFTWARE 1 xx 26 05 2015 FOR SOLAR COLLECTORS INSTALLATION AND OPERATION MANUAL...

Page 2: ......

Page 3: ...diagram of connections 16 12 1 1 Use of connectors 17 12 1 2 Power supply connection 17 12 1 3 Temperature sensor connection 17 13 HOW TO CLOSE CASING 18 14 FUSE REPLACEMENT 19 15 TROUBLESHOOTING 20 L...

Page 4: ...c system to which the controller is connected must be protected with a cut out device suitable for expected loads Never use the controller when its casing is damaged In any case do not alter the contr...

Page 5: ...and electronic products disposal system It is recommended to process in accordance with local regulations and not to dispose used products to household garbage containers Proper disposal of outdated...

Page 6: ...6...

Page 7: ...OPERATING MANUAL PCSol 150...

Page 8: ...long with the temperature rise Measured temperature is shown with the step of 10 C for T1 sensor collector s temperature and 5 C for T2 sensor DHW reservoir temperature Subsequent segments of the indi...

Page 9: ...llector temperature TCOLmin move the cursor to the indicator with sun symbol Press the knob sun symbol will start fast blinking to enter value editing mode You may change the value by turning the knob...

Page 10: ...ted by illumination of the sun symbol indicator When the collector temperature drops two degrees below minimal temperature preset the sun symbol will go off and the controller will disable the collect...

Page 11: ...n interruption Alarm on incorrect operation or damage to T2 sensor Signals interruption in T2 sensor circuit Check if the sensor is not e g off the unit or the connecting wire is cut Collector pump op...

Page 12: ...roller off the pump operation will be stopped 9 1 Test of unit When switched on the unit undergoes some testing At the time the display shows alternately the testing screen and the software version Te...

Page 13: ...INSTALLATION MANUAL PCSol 150...

Page 14: ...the set Controller PCSol 150 Temperature sensor T1 CT6w Temperature sensor T2 CT6 Installation and operating manual 1 pc 1 pc 1 pc 1 pc 11 INSTALLATION The controller is designed for operation in the...

Page 15: ...ust and water access is prevented Permissible operating temperature is not exceeded 40 C for controller Air exchange inside casing is allowed Access to dangerous parts is disabled Electrical installat...

Page 16: ...in sections 12 1 2 12 1 3 Presented hydraulic diagram will not replace central heating technical design and may be used only for informative purposes Collector and hot water reservoir must be install...

Page 17: ...act surfaces with temperatures that exceed the cables operating temperature limits The controller has no PE protective connector because the controller itself does not require grounding PE terminals o...

Page 18: ...r must be located in thermometric tube between the supply and return connectors of the collector exchanger pipe coil The sensors resistance per temperature table CT6w CT6 Temp C Min Nom Max 0 999 7 10...

Page 19: ...t means that the fuse is burnt and must be replaced For the unit use sub miniature slow blow fuse 1 25A compliant to IEC 60127 and with maximum switching current not lower than 100A Example of such fu...

Page 20: ...Collector pump capacity is too low pump is not able to transfer heat to reservoir exchanger 3 Temperature preset for reservoir has been reached and controller has disabled the pump Collector pump is...

Page 21: ...Presented drawing is in 1 1 scale and it may be helpful during installation You may cut off this page and use to mark installation place Fig 15 1 Casing drawing for installation aid...

Page 22: ......

Page 23: ......

Page 24: ...SALUS Controls Made in Poland...

Reviews: