67
23.
THERMOSTAT
REJECTED WC
Thermostat was rejected by the
wiring centre.
• Perform the thermostat’s pairing procedure again.
24.
CONNECTIVITY
LOST
Thermostat has lost connection with
the nearest 230V powered device.
• Check the power supply of the nearest 230V device. If there is problem
with RF signal range, install the ZigBee Network Repeater and pair
thermostat with the receiver again (wiring centre, TRV head etc.)
25-28.
CONNECTIVITY
LOST ZONE
9-12
Wiring centre has lost connection
with thermostat of the given zone:
e.g. 26 = with zone 9; 27 = with
zone 10; 28 = with zone 11, 29 =
with zone 12. Error is displayed on all
thermostats.
• Check the thermostat’s power supply.
• Send the heating signal from thermostat.
• If necessary, reinstall the thermostat.
29.
TRV GEAR
DEFECT
TRV head has a problem with the
internal gear mechanism.
• Reinstall the TRV head or replace it. If necessary, contact with the
SALUS Technical Department.
30.
TRV FAILED
ADAPTATION
Adaptation error of the TRV head
assembled on the radiator valve
insert.
• Check assembly of the TRV head on radiator valve insert and reinstall
the TRV head.
• Check the compatibility of the TRV head and radiator valve insert;
replace the valve insert if necessary.
31.
THERMOSTAT
LOW BATTERY
Thermostat’s battery level is low
(error is displayed only in the Smart
Home application).
• Replace thermostat batteries.
32.
CONNECTIVITY
LOST RX10RF
The RX10RF receiver has lost
connection with thermostat (error
is displayed only in the Smart Home
application).
• Check the thermostat’s power supply.
• Force identification process from the coordinator/gateway side and
check if devices are within the network.
• Send the heating signal from thermostat side and check if RX10RF
receiver is turning ON.
• If the top LED diode is flashing, perform the pairing procedure
according to the RX10RF manual instruction.
• Pair thermostat with the RX10RF receiver again according to the ther-
mostat’s manual instruction.
ERROR
CODE
DISPLAY
DESCRIPTION
ERROR DESCRIPTION
TROUBLESHOOTING
21.
TRV
LOW BATTERY
Low battery level in the TRV head.
• Replace TRV head batteries.
22.
UNPAIRED TRV
WITHIN RANGE
TRV head’s pairing error or head is
incompatible with the system.
• Remove TRV head from the system and repeat pairing procedure with
thermostat.
20.
CONNECTIVITY
LOST COORD.
TRV head has lost connection with
CO10RF coordinator/UGE600 internet
gateway.
• Check TRV head batteries (replace if necessary).
• Check if the coordinator/ internet gateway is connected to the power
supply.
• Force identification process from the coordinator/gateway side and
check if devices are within the network.
• Send the heating signal from thermostat.