9-5
P16 - AWAY Mode
Fan Coil Thermostat terminals Ts and Tc are used to initiate or terminate an Away state in the device . The
Ts/Tc contact closure is configured by P16 as a Normally Open or Normally Closed contact, or as an input
to be ignored .
Table 9.4: AWAY Mode Function
P16
Ts/Tc
Status
P21
0 (Setback Mode)
1(Off Mode)
0 (Disabled)
Ignored
Inactive
Inactive
1 (Normally Closed)
Open
Setback
Off
Close
Inactive
Inactive
2 (Normally Open)
Open
Inactive
Inactive
Close
Setback
Off
A contact state change detected between the two terminals will initiate the Away timers (P19 or P20)
and once the timers expire, the device will enter or exit AWAY mode (indicated by the “person in doorway”
icon) . The timers are canceled if the contact input changes while the timers are active .
If Setback is selected when in AWAY mode (P21), the Setback set points (P17 and P18) will be in effect
(indicated by “leaf” icon), overriding any schedules .
Section 9
SC102ZB/ST103ZB Installation and Operation Manual
Operation