background image

   

Screw

 4.  There are two mounting holes located at the back 

housing. Mark their locations on the wall where the 

thermostat to be installed. Drill two 6mm holes, insert 

the wall anchors provided, and then mount the ther-

mostat on the wall using the two mounting screws.

   

 

 Note:

 Wall anchors are not needed if the thermostat 

is mounted on a wooden wall. In this case drill two 

2.6 mm holes instead of 6mm.

 5. Wiring: The  thermostat  is  designed  to  switch 

230VAC/7A maximum. Never exceed the limit 

or  it  will  damage  the  termostat  or  cause  fire. 

The  three  terminals  of  the  thermostat  are  la-

beled NIN (Neutral Input), LIN (Live Input) and 

LOUT  (Live  Output).  Identify  the  wires  and 

connect  them  to  the  thermostat  accordingly.

   IMPORTANT: Ensure that the electric supply is cut 

off before installing the thermostat.

 6. Turn the knob so that the marking on the dial meet 

the one on the housing, replace the front cover and 

tighten the screw.

   

 7. Turn on the electric supply. The Heating Indicator 

(red LED) will flash twice which indicates successful 

installation. The thermostat will then enter a “warm-

up” mode (lasts about 3 to 10 seconds, depending 

on different conditions). It is indicated by turning on 

the Heating indicator.

   Note: If the LED fails to flash, cut off the electric 

supply and retry after 30 seconds. (“To cut off” the 

electric supply means to cut off the electric input 

to the thermostat terminals, but not by setting the 

thermostat switch to OFF.)

    THERMOSTAT TH-3 
Line Voltage Thermostat with Setback function

Instruction Manual

TH-3 Line Voltage Thermostats are designed for tempe-

rature control of a heating system. The device incorpo-

rates HEAT/OFF function selection. TH-3 also includes 

the feature of set-back temperature for energy saving 

purposes. The thermostats are intended for indoor use. 

Typical applications include residential quarters, offices, 

schools, workshops and retail outlets, etc.

Technical data

Type: 

230VAC Line voltage thermostat  

 

for single stage heating system

Temperature control range: 

5°C - 30°C

Set-back Temperature (TH-3):  5 °C

Set-back period (TH-3):  

6 hours, repeated  

 

 

daily

Maximum switching voltage:  250VAC, 50/60Hz

Maximum switching current: 

7A resistive,  

 

 

 

3A inductive

Control switch: 

 

MCU controlled    

 

 

relay switch

System indication:  Output status indicated by an  

LED Set-back condition  

indicated by a bicolor LED  for 

indication of set-back mode 

and set-back temperature

Operating temperature: 

0°C to 40°C

Storage temperature: 

-20°C to 60°C

Installation instructions

 1. IMPORTANT: Ensure that the electric supply is cut 

off before installing the thermostat

 2. Select a suitable location for the thermostat: it should 

be where free air can be reached and far away from 

heat sources, e.g., TV set, furnace or direct sun 

light, etc. It is recommended that the thermostat be 

mounted about 1.5m above the floor.

 3. Open the front cover of the thermostat by removing 

the screw at the bottom of the thermostat.

GB

IM-TH3-GB-01

Operating Instruction

 

 1. To turn on thermostat control, set the Slide Switch to 

HEAT. This will enable the room temperature control.

 2. To turn off the thermostat control, set the Slide Switch 

to OFF. This will turn off the room temperature control 

(heating system will always turn off).

 3. Room temperature is adjusted by setting the Tem-

perature Setting Dial.

 4. When the heating system is turned on, the Heating 

Indicator will turn on.

   Note: To prevent rapid cycling, there is a built-in swit-

ching time delay. The thermostat may not respond 

instantly when the temperature setting is changed.

Automatic Setback temperature

Setback temperature is an energy saving feature. It 

lowers the room temperature at night (to save ener-

gy) and returns to normal setting in the daytime (for 

comfort).

The Setback temperature of TH-3 is 5 degrees lower 

than the current dial setting. i.e., If the dial is set at 22°C, 

then the Setback temperature is 17°C. The Setback 

period of TH-3 is 6 hours.i.e., If the thermostat changes 

to Setback temperature at 23:00, then it will return to 

normal setting at 05:00. The Setback - normal tempera-

ture cycling will repeat everyday until it is disabled.

Operation:

 1. Press the Setback Button „)“ to change to Set-back 

temperature. The Setback Indicator (bicolor LED) 

will turn yellow.

 2. Six hours later after changing to Set-back temperatu-

re, it will return to normal temperature. The Setback 

Indicator will change to green.

 3. At the same time next day, the thermostat will return 

to Setback temperature again.

 4. To disable setback temperature, press Setback Buton 

again. The Set-back Indicator will turn off

Salus Controls plc

Salus House,

Dodworth Business Park South,

Dodworth, Barnsley, S75 3SP

Web: www.salus-tech.com

All manuals and user guides at all-guides.com

all-guides.com

Reviews: