Assembly and commissioning
Page 23/55
Assembly and commissioning
These assembly steps apply in principle to the assembly of all variants:
Make all necessary connections and installations as described on pages 23 ff.
Use the installation examples on the following pages.
Take measures to ensure that the module can only be put into operation together with the fan
of the ventilation system.
After completing the installation, check your system for error-free and desired function.
Check the earthing for
proper function (conductive resistance: < 5 Ω).
If there are still errors, correct these errors and check the installation again to make sure it is
free of errors.
Carry out the error check until all errors have been eliminated.
ATTENTION
Risk of injury is possible.
There is a risk of injury during assembly.
Use appropriate PPE (protective gloves, UV eye protection).
CAUTION
Risk of injury is possible.
If you continue to operate the ventilation system before mounting the module, there is
a risk of injury.
Switch off the unit before carrying out any work on the unit.
WARNING
Dangerous malfunctions are possible.
If the system is not installed and commissioned by a qualified specialist company,
dangerous malfunctions with fatal consequences are possible.
Follow the instructions below.
WARNING
Hazardous ozone emissions are possible.
If the module is operated outside the ventilation system, ozone poisoning and as-
phyxiation are possible.
Do not put the module into operation until it has been completely and fault-
lessly installed in the ventilation system.
OZON