38 | SAMLEX AMERICA INC.
APPENDIX A
Output short circuit!
EVO Inverter Charger is in
FAULT MODE
because there is a short circuit on the
output side in
Inverter Mode
. Short circuit protection is activated when the output
current is over 18.33Arms and output voltage is less than 15 Vrms for 6 cycles (0.1
second for 60 Hz)
• There is no AC output because the Inverter Section has been switched OFF.
The Green LED marked “Status” will be switched OFF and the Red LED marked
“Alarm” will be steady ON. The buzzer in EVO Inverter Charger will beep steady
• EVO Inverter Charger will be latched in OFF condition and will require
manual reset by powering OFF, waiting for 1 minute and then powering
ON again
NOTE:
If there is short circuit condition in Charging Mode i.e. when AC input is avail-
able, short circuit condition on the output side will trip the AC input breaker. The load
will be transferred to the Inverter Section and the Inverter Section will then see short
circuit condition and will shut down as described above
Output failure!
EVO Inverter Charger is in
FAULT MODE
because AC input from Grid / Generator has
been connected to the AC Output terminals by mistake. 10VAC or above seen at the
AC Output Terminals
at the time of boot up of EVO Inverter Charger
will activate
this protection
• The Green LED marked “Status” will be switched OFF and the Red LED marked
“Alarm” will be steady ON. The buzzer in EVO Inverter Charger will beep steady
• EVO Inverter Charger will be latched in OFF condition and will require manual
reset by powering OFF, waiting for 1 minute and then powering ON again
Check the connection. If there is 10V over at the output terminal, remove the connection.
Transformer over heat!
EVO Inverter Charger is in
FAULT MODE
because the main Bidirectional Transformer
in the EVO Inverter Charger has overheated to 150°C
• The Green LED marked “Status” will be switched OFF and the Red LED marked
“Alarm” will be steady ON. The buzzer in EVO Inverter Charger will beep steady
• If in Inverting Mode, Inverter Section will be switched OFF. If in Charging Mode, the
Transfer Relay will be de-energized and the Inverter Section will be switched OFF.
• Check that the fans are working properly, there is no blockage of air suction and
discharge vents, adequate cool replacement air is available and the ambient tem-
perature is within the limits. Reduce the load / “BULK CURRENT” (Section 4.4)
• The fault will be cleared when the transformer has cooled down to 80°C
Heat sink over heat!
EVO Inverter Charger is in
FAULT MODE
because the internal heat sink in the EVO
Inverter Charger has overheated to 60°C
• The Green LED marked “Status” will be switched OFF and the Red LED marked
“Alarm” will be steady ON. The buzzer in EVO Inverter Charger will beep steady
• If in Inverting Mode, Inverter Section will be switched OFF. If in Charging Mode, the
Transfer Relay will be de-energized and the Inverter Section will be switched OFF.
• Check that the fans are working properly, there is no blockage of air suction and
discharge vents, adequate cool replacement air is available and the ambient tem-
perature is within the limits. Reduce the load and “BULK CURRENT” (Section 4.4)
• The fault will be cleared when the heat sink has cooled down to 40°C
SD card unusable!
• Data logging will not start.
• Check that the format is FAT16/FAT32.
• Check that the capacity is less than 16 GB.
• Re-format the card.
SD card read error!
• Data logging stops.
• Remove and re-insert the card.
SD card write error!
• Data logging stops.
• Remove and re-insert the card.
SD card full!
• Data logging stops.
• Move or delete files or re-format the card.
SECTION 7 |
Fault Messages and
Troubleshooting Guide