80 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 81
TABLE 6.1 LED AND BUZZER INDICATIONS
Status
Green LED
marked “ON”
(12, Fig 2.1)
Red LED
marked
“Fault” (13, Fig
2.1)
Buzzer
When powered ON
Flash 3 times
Off
Off
When powered OFF
On
On
Off
Normal charging
Flash 1 time per sec Off
Off
Equalization charging
Flash 2 times per
sec
Off
Off
Inverting (Discharging)
On
Off
Beep per 3 second
(Default Off)
Low battery alarm
On
Flash 1 per sec
Beep per 1 second
Power saving
Flash 1 time per
3 sec
Off
Off
Standby
Off
Off
Off
Fault
Off
On
On
6.4 OPTIONAL REMOTE CONTROL EVO-RC (see Appendix A) FOR PRO-
GRAMMING OF MODES OF OPERATION AND PARAMETERS
Optional Remote Control Model EVO-RC (Fig 2.4) will be required for more advanced control
and monitoring. Please see separate Owner’s Manual for EVO-RC at Appendix A. The Remote
Control comes with 10M / 33 ft., RJ-45 Data Cable. The Remote plugs into RJ-45 Jack on the
front panel of the unit (7, Fig 2.1). It has provision for Data Logging using SD Card of up to
16 GB (FAT16 / FAT32). It also has its own Real Time Clock and Super Capacitor Type of Bat-
tery.
Detailed messaging is available through its LCD display and LEDs. This remote will also be
required for programming of various parameters to suit specific requirements. Each program-
mable parameter has a Default Value. This unit has been shipped with the various parameters
set at the Default Values. Programmable and Default values are shown in Tables 6.2 to 6.6
below:
TABLE 6.2 PROGRAMMABLE AND DEFAULT PARAMETERS: GROUP CHARGING CURVE
Parameter
Programming Range
(Programming requires optional Re-
mote Control Model EVO-RC)
Default
EVO-
2212
EVO-
3012
EVO-
2224
EVO-
4024
EVO-
2212
EVO-
3012
EVO-
2224
EVO-
4024
“BULK CURRENT” **
(Bulk Charge Current “Io”)
0-100A
0-130A
0-70A
0-110A
40A
“ABSORP VOLTAGE” **
(Absorption Voltage)
13.5V - 16.0V
27.0V - 32.0V
14.0V
27.6V
“EQUALIZE VOLTAGE” **
(Equalization Voltage)
14.0V - 16.0V
28.0V - 32.0V
15.3V
29.2V
“FLOATING VOLTAGE" **
(Float Voltage)
13.0V - 15.0V
26.0V - 30.0V
13.8V
27.0V
“COMPENSATE”
(Temperature Compensation)
-3mV to -5mV /°C/Cell
-4mV /°C/Cell
“LOW VOLT ALARM”
(Battery Low Voltage Alarm)
9.5V - 12.5V
19.0V - 25.0V
11.0V
22.0V
“BATT LOW VOLTAGE”
(Battery Low Voltage Shut
Down)
>9.0V - 12.0V
>18.0V - 24.0V
10.5V
21.0V
“LV DETECT TIME”
(Low Voltage Detect Time)
0-600 sec
10 sec
“LV CUT OFF TIME”
(Low Voltage Cut Off Time)
0-7200 sec
1200 sec
“RESET VOLTAGE”
(Battery Low Voltage Reset)
12.0V - 17.0V
24.0V - 35.0V
12.5V
25.0V
“BATT OVER VOLT”
(Battery Over Voltage Shut
Down)
14.0V - 17.0V
28.0V - 35.0V
16.0V
32.0V
“CHARGE MODE”
( 3 or 4 Stage Charging)
Normal (3-Stage) / Equalization (4-Stage)
Normal (3-Stage)
"ON LINE MODE"
0 = OFF 1 = ON
0 = OFF
"RECONNECT VOLT"
(For On-Line Mode)
13.50V to 16.00V
27.00V to 32.00V
14.00V
27.60V
SECTION 6 |
Operation, Protections and Troubleshooting