20 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 21
APPENDIX A
SECtION 4 |
Parameter Setup
•
Heat Sink:
In cast the temperature is >65C, the charging current is reduced by 4A
(EVO-2212) / 20A (EVO-3012) / 1A (EVO-2224) / 5A (EVO-4024) every 10 sec
ABSoRP VoLtAGe:
This sets the charging voltage in the Constant Voltage Absorption Stage.
SELECT GROUP
CHARGE CURVE
BULK CURRENT
40 A
ABSORP VOLTAGE
14.40 V
KEY IN PASSWORD
0000
Enter Key
ò
Enter Key
ò
ABSORP VOLTAGE
14.40 V
ò
Up Key x 1
ò
Password 8052
See Section 4.3.1
eQUALiZe VoLtAGe:
This sets the charging voltage in the Constant Voltage Stage in the 4-stage Equalization
Charging Stage.
SELECT GROUP
CHARGE CURVE
BULK CURRENT
40 A
EQUALIZE VOLTAGE
14.40 V
Enter Key
ò
Up Key x 2
ò
KEY IN PASSWORD
0000
Enter Key
ò
EQUALIZE VOLTAGE
14.40 V
ò
Password 8052
See Section 4.3.1
FLoAtinG VoLtAGe:
This sets the charging voltage in the Constant Voltage Float Stage.
SELECT GROUP
CHARGE CURVE
BULK CURRENT
40 A
FLOATING VOLTAGE
13.50 V
Enter Key
ò
Up Key x 3
ò
KEY IN PASSWORD
0000
Enter Key
ò
FLOATING VOLTAGE
13.50 V
ò
Password 8052
See Section 4.3.1
CoMPenSAte:
This parameter sets the temperature compensation for the battery. The operational range of
the EVO
TM
Inverter/Charger is -20°C to 60°C.
This compensation voltage will affect the Absorbtion Voltage/Equalize Voltage/Floating Voltage/
Batt Over Volt/Restart Voltage/Low Volt Alarm/Batt Low Voltage when the Temperature Sensor
is installed on the battery (see Fig 2.5 in the Owner's Manual for Evolution
TM
Series Inverter/
Charger).
SELECT GROUP
CHARGE CURVE
BULK CURRENT
40 A
COMPENSATE
4
Enter Key
ò
Up Key x 4
ò
mV/C/C
COMPENSATE
4
mV/C/C
KEY IN PASSWORD
0000
Enter Key
ò
ò
Password 8052
See Section 4.3.1
BAtt oVeR VoLt:
This parameter sets the upper battery voltage threshold at which inverting / charging
operations are switched OFF to protect the unit against damage due to battery overvoltage:
•
AC input is not available and eVo
TM
inverter/Charger is operating in inverting
Mode:
When the battery voltage rises to the set upper threshold of “BATT OVER VOLT”,
the Inverter Section will be shut down and fault message “Battery over voltage!” will be
displayed on the LCD screen. The Green LED marked “Status” will switch OFF and the
Red LED marked “Fault” will remain ON steady. The buzzer on EVO
TM
Inverter/Charger will
beep steady. The fault will be cleared automatically when the battery voltage drops to 0.5V
below the set upper threshold of “BATT OVER VOLT”