26 | SAMLEX AMERICA INC.
APPENDIX A
SECtION 4 |
Parameter Setup
•
Automatic Starting and Stopping of Generator:
Switching ON (energizing) the
Status Relay to initiate Generator starting
•
on-Line Mode:
Switching ON of the Transfer Relay to transfer from “Inverting” Mode
to “Charging” Mode
SELECT GROUP
CHARGE CURVE
BULK CURRENT
40A
GS DETECT TIME
10 sec
Enter Key
ò
Up Key x 15
ò
GS DETECT TIME
010 sec
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
Gen on tiMe
This parameter is a Programmable Timer (0-240min; Default: 60 min) that is used for program-
ming Automatic Starting and Stopping of Generator (Section 4.8 under “Relay Function”:
4=Generator 2). The Timer sets the duration the Generator will remain ON from the time the
Status Relay has been switched ON (energized). The Status Relay will switch ON (energize) and
start the Generator if the battery voltage remains at threshold of “LOW VOLT ALARM” condi-
tion [(i) for 12V: 9.5V – 12.5V / Default 11.0V (ii) for 24V: 19.0V – 25.0V / Default 22.0V], or
lower for continuous period = “GS DETECT TIME” (0 – 600sec; Default 10 sec)
SELECT GROUP
CHARGE CURVE
BULK CURRENT
40A
GEN ON TIME
60 min
Enter Key
ò
Up Key x 16
ò
GEN ON TIME
060 min
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
Gen oFF DeLAY
This parameter is a Programmable Timer (0-240min; Default: 60 min) that is used for the following:
•
Programming Automatic Starting and Stopping of Generator (Section 4.8 under
“Relay Function”: 3=Generator 1):
The Timer sets the time period the batteries are
required to remain charged at the desired programmed level of voltage = “RESET VOLT-
AGE” [(i) for 12V: 12.0V – 17.0V / Default 14.0V (ii) for 24V: 24.0V – 35.0V / Default
28.0V], or higher before the Status Relay is switched OFF (de-energized) to stop the
Generator.
•
Programming option 2 in on-Line / off Line UPS Modes (Section 4.4: 1=option 2):
The
Timer sets the time period the batteries are required to remain charged at the desired
programmed level of voltage = “RESET VOLTAGE” [(i) for 12V: 12.0V – 17.0V / Default
14.0V (ii) for 24V: 24.0V – 35.0V / Default 28.0V], or higher before the Transfer Relay is
switched OFF (de-energized) to exit “Charging” Mode and revert to “Inverting” Mode.
SELECT GROUP
CHARGE CURVE
BULK CURRENT
40A
GEN OFF DELAY
60 min
Enter Key
ò
Up Key x 17
ò
GEN OFF DELAY
060 min
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1