28 | SAMLEX AMERICA INC.
APPENDIX A
SECtION 4 |
Parameter Setup
Gen MAX CURRent:
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT SETTING
GEN MAX CURRENT
16.00 A
DEFAUT FREQ
0= 50Hz
Up Key
ò
Enter Key
ò
Up Key x 2
ò
GEN MAX CURRENT
16.00 A
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
HiGH CUt oFF:
If the AC input frequency is over the value of “HIGH CUT OFF” when in "Charging Mode",
the EVO
TM
Inverter/Charger will transfer to Inverting Mode.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT SETTING
HIGH CUT OFF
55.00 Hz
DEFAUT FREQ
0= 50 Hz
Up Key
ò
Enter Key
ò
Up Key x 3
ò
HIGH CUT OFF
55.00 Hz
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
HiGH ReSet:
This is the reset frequency at which the unit will revert to "Charging Mode" after it has
switched over to "Inverter Mode" due to input frequency rising above "HIGH CUT OFF".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT SETTING
HIGH RESET
54.00 Hz
DEFAUT FREQ
0= 50 Hz
Up Key
ò
Enter Key
ò
Up Key x 4
ò
HIGH RESET
54.00 Hz
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
LoW CUt oFF:
If the AC input frequency is below “LOW CUT OFF” value when in "Charging Mode", the
EVO
TM
Inverter/Charger will transfer to Inverting Mode.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT SETTING
LOW CUT OFF
45.00 Hz
DEFAUT FREQ
0= 50 Hz
Up Key
ò
Enter Key
ò
Up Key x 5
ò
LOW CUT OFF
45.00 Hz
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
LoW ReSet:
This is the reset frequency at which the unit will revert to "Charging Mode" after it has
switched over to "Inverting Mode" due to input frequency falling below "LOW CUT OFF".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT SETTING
LOW RESET
46.00 Hz
DEFAUT FREQ
0= 50 Hz
Up Key
ò
Enter Key
ò
Up Key x 6
ò
LOW RESET
46.00 Hz
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
4.6 GRoUP 3 PARAMeteR Set UP: inPUt LoW LiMit
Please refer to Parameters under Group 3 at Fig 4.1. Details of Parameter set up are given below:
tABLe 4.6. GRoUP 3 PARAMeteR Set UP: inPUt LoW LiMit
Screen
no. for
Group
3 (Fig
4.1)
Parameter
Setting range
Default value
eVo-
2212e
eVo-
3012e
eVo-
2224e
eVo-
4024e
eVo-
2212e
eVo-
3012e
eVo-
2224e
eVo-
4024e
1
ReSet VoLtAGe
140.0 – 200.0V
190.0V
2
CUt oFF VoLt 1
140.0 – 200.0V
180.0V
3
DeteCt tiMe 1
0 – 2000 cycles
300 cycles
4
CUt oFF VoLt 2
140.0 – 200.0V
170.0V
5
DeteCt tiMe 2
0 – 2000 cycles
60 cycles
6
CUt oFF VoLt 3
140.0 – 200.0V
160.0V
7
DeteCt tiMe 3
0 – 2000 cycles
1 cycle