28 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 29
APPENDIX A
ReSet VoLtAGe:
This is the reset voltage at which the unit will revert to "Charging Mode" after it has
switched over to "Inverting Mode" due to input voltage falling to "CUT-OFF VOLT 1/CUT-OFF
VOLT 2/CUT-OFF VOLT3".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
RESET VOLTAGE
190.0 V
Up Key x 2
ò
Enter Key
ò
RESET VOLTAGE
190.0 V
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
CUt oFF VoLt 1:
If during "Charging Mode", the AC input voltage falls below "CUT-OFF VOLT 1" for period >
"DETECT TIME 1", the EVO
TM
Inverter/Charger will transfer to Inverting Mode from "Charging
Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
CUT OFF VOLT 1
180.0 V
RESET VOLTAGE
190.0 V
Up Key x 2
ò
Enter Key
ò
Up Key x 1
ò
CUT OFF VOLT 1
180.0 V
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
DeteCt tiMe 1:
This is the time limit in cycles up to which low AC input voltage "CUT-OFF VOLT 1" is allowed.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
DETECT TIME 1
300 cycles
RESET VOLTAGE
190.0 V
Up Key x 2
ò
Enter Key
ò
Up Key x 2
ò
DETECT TIME 1
0300 cycles
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
CUt oFF VoLt 2:
If during "Charging Mode", the AC input voltage falls below "CUT-OFF VOLT 2" for period >
"DETECT TIME 2", the EVO
TM
Inverter/Charger will transfer to "Inverting Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
CUT OFF VOLT 2
170.0 V
RESET VOLTAGE
190.0 V
Up Key x 2
ò
Enter Key
ò
Up Key x 3
ò
CUT OFF VOLT 2
170.0 V
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
DeteCt tiMe 2:
This is the time limit in cycles up to which low AC input voltage "CUT-OFF 2" is allowed.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
DETECT TIME 2
60 cycles
RESET VOLTAGE
190.0 V
Up Key x 2
ò
Enter Key
ò
Up Key x 4
ò
DETECT TIME 2
0060 cycles
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
CUt oFF VoLt 3:
If during "Charging Mode", the AC input voltage falls below "CUT-OFF VOLT 3" for period >
"DETECT TIME 3", the EVO
TM
Inverter/Charger will transfer to "Inverting Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
CUT OFF VOLT 3
160.0 V
RESET VOLTAGE
190.0 V
Up Key x 2
ò
Enter Key
ò
Up Key x 5
ò
CUT OFF VOLT 3
160.0 V
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
DeteCt tiMe 3:
This is the time limit in cycles up to which the low AC input voltage "CUT-OFF 3" is allowed.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
DETECT TIME 3
1 cycle
RESET VOLTAGE
190.0 V
Up Key x 2
ò
Enter Key
ò
Up Key x 6
ò
DETECT TIME 3
0001 cycle
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
SECtION 4 |
Parameter Setup