30 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 31
APPENDIX A
DeteCt tiMe 2:
This is the time limit in cycles up to which high AC input voltage "CUT-OFF VOLT 2" is allowed.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT HIGH LIMIT
DETECT TIME 2
15 cycle
RESET VOLTAGE
260.0 V
Up Key x 3
ò
Enter Key
ò
Up Key x 4
ò
DETECT TIME 2
0015 cycle
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
CUt oFF VoLt 3:
If during "Charging Mode", the AC input voltage rises above "CUT-OFF VOLT 3" for period >
"DETECT TIME 3", the EVO
TM
Inverter/Charger will transfer to "Inverting Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT HIGH LIMIT
CUT OFF VOLT 3
275.0 V
RESET VOLTAGE
260.0 V
Up Key x 3
ò
Enter Key
ò
Up Key x 5
ò
CUT OFF VOLT 3
275.0 V
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
DeteCt tiMe 3:
This is the time limit in cycles up to which high AC input voltage "CUT-OFF VOLT 3" is allowed.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT HIGH LIMIT
DETECT TIME 3
1 cycle
RESET VOLTAGE
260.0 V
Up Key x 3
ò
Enter Key
ò
Up Key x 6
ò
DETECT TIME 3
0001 cycle
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
4.8 GRoUP 5 PARAMeteR Set UP: otHeR FUnCtionS
Please refer to Parameters under Group 5 at Fig 4.2. Details of Parameter set up are given below:
tABLe 4.8. GRoUP 5 PARAMeteR Set UP: otHeR FUnCtionS
Screen
no. for
Group 5
(Fig 4.2)
Parameter
Setting range
Default value
eVo-
2212e
eVo-
3012e
eVo-
2224e
eVo-
4024e
eVo-
2212e
eVo-
3012e
eVo-
2224e
eVo-
4024e
1
PoWeR SAVinG
1 = Enable 0 = Disable
0 = Disable
2
enteR Point
4 – 50W
6W
8W
6W
8W
3
WAKe UP Point
5 – 50W
7W
10W
7W
10W
4
ReMote SWitCH
0 = Button Type
1 = Switch Type
Button type
5
ReLAY FUnCtion
0 = Charge/Other
1 = Normal/Fault
2 = Generator 0
3 = Generator 1
4 = Generator 2
2 = Generator 0
6
CoMM iD
1 – 255
1
7
BUZZeR
1 = ON
0 = OFF
1 = ON
8
DiSCHARGe BeeP
1 = ON
0 = OFF
0 = OFF
9
DeFAULt ReSet
0 = No
1 = Yes
0 = No
10
DAtALoG DiSABLe
DAtALoG tiMe
0 = Disable, 1 = 1 sec,
2 = 10 sec, 3 = 30 sec
4 = 1 min, 5 = 5 min, 6 = 10 min
1 = 1 sec
11
PARAMeteR SAVe
0 = No
1 = Yes
0 = No
SECtION 4 |
Parameter Setup