36 | SAMLEX AMERICA INC.
APPENDIX A
4= Generator 2
This Function will start the Generator at “LOW VOLT ALARM” and stop the Generator after the
desired programmed value of run time of the Generator = “GEN ON TIME” (0-240 min; Default
= 60 min) counted from the time the Status Relay is switched ON (energized)
• If the battery voltage drops to “LOW VOLT ALARM” [(i) for 12V: 9.5V – 12.5V / Default
11.0V (ii) for 24V: 19.0V – 25.0V / Default 22.0V] or lower for continuous period =
“GS DETECT TIME” (0-600 sec; Default 10 sec), the Status Relay will be switched ON
(energized). “Common” and “NO” contacts of the Status Relay will close to initiate
automatic starting of the Generator
• Once the generator has started and starts feeding AC output (within the programmed
limits of voltage and frequency), the EVO
TM
will change over from “Inverting Mode” to
“Charging Mode”. Battery charging will be initiated as per full and complete 3-Stage
Charging Algorithm (“CHARGE MODE” 0=Normal).
• The Status Relay will be switched OFF (de-energized) after expiry of the desired
programmed Generator run time = “GEN ON TIME” (0-240 min; Default = 60 min)
counted from the time the Status Relay is switched ON (energized). “Common” and
“NO” contacts of the Status Relay will open to initiate automatic stopping of the
Generator. When AC output from the Generator switches OFF, EVO
TM
will change over to
“Inverting Mode” (NOTE: The State of Charge of the battery after the Status Relay has
been switched OFF (de-energized) and Generator is stopped will be indeterminate).
Diagram showing steps for programming the above RELAY FUNCTION is given below:
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
RELAY FUNCTION
2 = Generator 0
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
Up Key x 4
ò
RELAY FUNCTION
2 = Generator 0
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
CoMM iD:
Communication ID- This sets the ID number for the COMM Port and EVO-RC Remote Control.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
COMM. ID
1
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
Up Key x 5
ò
COMM. ID
001
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
BUZZeR:
Set the buzzer ON/OFF.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
BUZZER
1 = On
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
Up Key x 6
ò
BUZZER
1 = On
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
DiSCHARGe BeeP:
To select the buzzer ON/OFF while in "Inverting Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
DISCHARGE BEEP
0 = Off
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
Up Key x 7
ò
DISCHARGE BEEP
0 = Off
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
DeFAULt ReSet
This is to reset all of the parameters to the Default Values.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
DEFAULT RESET
0 = No
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
Up Key x 8
ò
DEFAULT RESET
0 = No
ò
KEY IN PASSWORD
0000
Enter Key
ò
Password 8052
See Section 4.3.1
SECtION 4 |
Parameter Setup