82 | SAMLEX AMErICA INC.
SAMLEX AMErICA INC. | 83
tAbLe 6.6 ProgrAMMAbLe AnD DeFAuLt PArAMeterS - grouP "other FunCtionS" (Continued)
Parameter name
Setting range
Default Value
eVo-
2212e
eVo-
3012e
eVo-
2224e
eVo-
4024e
eVo-
2212e
eVo-
3012e
eVo-
2224e
eVo-
4024e
“reLAy FunCtion”
(for Status relay)
3 = generator 1
ON when batteries drop to "LOW
VOLT ALArM" or lower for period
= "GS DETECT TIME" - initiates
Generator start
Off when batteries are charged
to "rESET VOLTAGE" for period =
"GEN Off TIME" - initiates Genera-
tor stop
4 = generator 2
ON when batteries drop to "LOW
VOLT ALArM" or lower for period
= "GS DETECT TIME" - initiates
Generator start
Off after period = "GEN ON TIME"
from the time relay switched ON -
initiates Generator stop
2
= Generator 0
“CoMM iD”
(Communication ID for
optional remote Control
EVO-rC)
1 - 255
1
“buZZer”
0 = Off ; 1 = ON
1 = On
“DiSChArge beeP”
(beeping in “Discharg-
ing / Inverter Mode”)
0 = Off ; 1 = ON
0 = Off
“DeFAuLt reSet”
0 = No ; 1 = Yes
0 = No
DAtA Log tiMe
(for Optional remote
Control EVO-rC)
0 = Disable 3 = 30 sec 6 = 10 min
1 = 1 sec 4 = 60 sec
1
2 = 10 sec 5 = 5 min
1
1 = 1 sec
PArAMeter SAVe
(for Optional remote
Control EVO-rC)
0 = No
1 = Yes
0 = No
6.5 ProteCtionS, FAuLt MeSSAgeS AnD troubLeShooting guiDe
The front panel of the unit has a red LED marked “fAULT” (13, fig 2.1). This LED will light
up (steady) when the unit registers any of the
FAuLt MoDe
situations shown in Table 7.1 of
EVO-rC Manual at Appendix A.
Table 7.1 of EVO-rC Manual at Appendix A shows details of protections and associated fault/
Error Messages that will be displayed on the LCD screen of the optional remote Control EVO-rC.
note:
If the optional remote Control EVO-rC (see Appendix A) is not used, it may be
difficult to narrow down the probable cause of the fault.
SECTIOn 6 |
Operation, Protections and Troubleshooting