26 | SAMLEX AMERICA INC.
APPENDIX A
SECTION 4 |
Parameter Setup
B U L K C U R R E N T
0 4 0 A
The 1
st
screen of parameter “BULK CURRENT” setting appears as shown on the left. For
EVO-2212/3012/4024, the upper limit of the programming range of parameter “BULK
CURRENT” is > 100A (see Table 4.1) and hence, 3 digits will be required to enter value of
100 A and above. Therefore, the default value of 40A will be displayed as “0 40” with
alternate blinking of the 1
st
digit between digit “0” and curser “_”
[NOTE: For EVO-2224,
the upper limit of the programming range of parameter “BULK CURRENT” is 70A (see
Table 4.1) and hence, 2 digits will be required. Therefore, the default value of 40A for
EVO-2224 will be displayed as 40 with alternate blinking of the 1
st
digit between digit “4”
and curser “_”]
To change the setting to new value of say 50A, the 3 digits will have to be changed from
“040” to “050” value
• As the 1
st
digit of the new setting “050” is “0”, there is no need to change this value.
Press the Enter Key
MOMENTARILY
to select “0” for the 1
st
digit. The blinking cursor
will automatically move to the 2
nd
digit “4” with alternate blinking of digit “4” and
curser “_”
• Press the Up Key to scroll the 2
nd
digit to “5”. Press the Enter Key
MOMENTARILY
to
select “5” for the 2
nd
digit. The blinking cursor will automatically move to the 3rd digit
“0” with alternate blinking of digit “0” and curser “_”
• As the 3rd digit of the new setting “050” is already “0”, there is no need to change
this value. Now the overall numerical value will be “050” with alternate blinking of
digit “0” and curser “_”
• Press the Enter Key,
HOLD for 3 to 4 sec
and then release to initiate writing of the
new value of 50A into the memory (See NOTE below)
NOTE:
When the last digit is changed to the desired digit (“0” in this case) by using the
Up / Down Keys,
the Enter Key has to be pressed continuously for 3 to 4 sec till message
“WRITE SUCCESS” is seen
. If the Enter Key is pressed momentarily or for shorter duration
(before “WRITE SUCCESS” message is seen), the value will NOT be written into the
memory and the cursor will move back to the 1st digit
WR I T E S U C C E S S !
5 0 A
Screen as shown on the left flashes twice when writing is successful.
B U L K C U R R E N T
5 0 A
Screen as shown on the left shows end of setting.
Press Back Key to go back to the previous menu level i.e. PARAMETER GROUP NO.1
(Displayed as"SELECT GROUP_CHARGE CURVE")
or Up/Down Key to any of the 23
PARAMETER SETUP SCREENS under the Sub-menu for PARAMETER GROUP NO.1
(Displayed as"SELECT GROUP_CHARGE CURVE")
.
B U L K C U R R E N T
!
9 0 A
An exclamation sign ‘!’ as shown in screen on the left is displayed when the parameter is
out of the specified programming range. For example, if 90A displayed was entered for
EVO-2224
(EVO-2224 range is 0-70A)
, it will be out of range and an exclamation sign ‘!’
will be displayed.
WR I T E F A I L U R E !
5 0 A
Screen as shown on the left flashes twice when there is a write failure.
O U T O F R A N G E !
9 0 A
Screen as shown on the left flashes twice when the set value is out of range.
(90A is out of
range for EVO-2224 because EVO-2224 range is 0-70A)
.
All programmable parameters
(See Parameter Setup Menu Maps at Figs 4.1 and 4.2)
and their Default Values are
described in Sections 4.4 to 4.10.