34 | SAMLEX AMERICA INC.
APPENDIX A
SECTION 4 |
Parameter Setup
4.4.2.11.2 Value of "LV CUT OFF TIME": 0 sec
4.4.2.11.2.1
When the value of parameter "LV CUT OFF TIME" is set at 0 sec, activation and resetting of Battery
low voltage!" fault condition
(Section 7, Srl.1 of Table 7.1)
will be as described in Section 4.4.2.9.2.
4.4.2.11.3 Programming Steps for Parameter "LV CUT OFF TIME"
Enter Key Enter Key Up Key x 10 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
B U L K C U R R E N T
4 0 A
ð
L V C U T O F F T I M E
1 2 0 0 s e c
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
L V C U T O F F T I M E
1 2 0 0 s e c
4.4.2.12 EQUALIZE – 4 STAGES
(Table 4.1, Parameter Setup Screen No. 12)
Please refer to Section 5.8.2 of EVO-2212/3012/2224/4024 Manual for background information on 4-Stage Adaptive
Charging Profile for Equalization
When AC input within the programmed window of voltage and frequency is available, EVO will operate as a battery
charger and charging will be carried out based on the selected option of parameter "CHARGING PROFILE". Parameter
"CHARGING PROFILE"
(Section 4.4.2.21)
allows option to select from 6 Charging Profiles - 3 profiles of 3-Stage and 3
profiles of 2-Stage charging. Default profile option is "0=3 Stage Adaptive”
4-Stage Adaptive Charging Profile for Equalization can be activated
AT ANY TIME
through programmable parameter
"EQUALIZE-4STAGES" set to "1=Yes". The Default Setting is "0=No" i.e. charging will be carried out as per 3 or
2-Stage profile that has been selected by parameter "CHARGING PROFILE"
(Section 4.4.2.21)
. After the 4-Stage
Adaptive Charging Profile for Equalization is completed, parameter "EQUALIZE-4STAGES" resets automatically to the
default setting i.e. Option "0=No" and the charging profile reverts to the last stage of the “CHARGING PROFILE” that
was active when 4-Stage Adaptive Charging Profile for Equalization was activated.
Details are given at Table 4.2 below: