40 | SAMLEX AMERICA INC.
APPENDIX A
SECTION 4 |
Parameter Setup
• Automatic Starting and Stopping of Generator:
Switching ON (energizing) the Status Relay to initiate
Generator starting
•
On-Line Mode:
Switching ON of the Transfer Relay to transfer from “Inverting” Mode to “Charging” Mode
4.4.2.16.1 Programming Steps for Parameter “GS DETECT TIME”
Enter Key Enter Key Up Key x 15 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
B U L K C U R R E N T
4 0 A
ð
G S D E T E C T T I M E
1 0 s e c
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
G S D E T E C T T I M E
0 1 0 s e c
4.4.2.17 GEN ON TIME
(Table 4.1, Parameter Setup Screen No. 17)
This parameter is a Programmable Timer
(0-240min; Default: 60 min)
that is used for programming Automatic Starting
and Stopping of Generator
(Section 4.8.2.5.2.3 under “Relay Function”: Option 4=Generator 2)
. The Timer sets the
duration the Generator will remain ON from the time the Status Relay has been switched ON (energized). The Status
Relay will switch ON (energize) and start the Generator if the battery voltage remains at threshold of “LOW VOLT
ALARM” condition
(Section 4.4.2.8)
, or lower for continuous period = “GS DETECT TIME”
(Section 4.4.2.16)
.
4.4.2.17.1 Programming Steps for Parameter “GEN ON TIME”
Enter Key Enter Key Up Key x 16 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
B U L K C U R R E N T
4 0 A
ð
G E N O N T I M E
6 0 m i n
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
G E N O N T I M E
0 6 0 m i n
4.4.2.18 GEN OFF DELAY
(Table 4.1, Parameter Setup Screen No. 18)
This parameter is a Programmable Timer
(0-240min; Default: 60 min)
that is used for the following:
• Programming Automatic Starting and Stopping of Generator
(Section 4.8.2.5.2.2 under “Relay Function”:
3=Generator 1)
:
The Timer sets the time period the batteries are required to remain charged at the desired
programmed level of voltage = “RESET VOLTAGE”
(Section 4.4.2.7)
, or higher before the Status Relay is switched
OFF (de-energized) to stop the Generator
• "ONLINE OPTION"
(Section 4.4.2.14)
; "1=Option 2":
The Timer sets the time period the batteries are required
to remain charged at the desired programmed level of voltage = “RESET VOLTAGE”
(Section 4.4.2.7)
, or higher
before the Transfer Relay is switched OFF (de-energized) to exit “Charging” Mode and revert to “Inverting”
Mode.
4.4.2.18.1 Programming Steps for Parameter “GEN OFF DELAY”
Enter Key Enter Key Up Key x 17 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
B U L K C U R R E N T
4 0 A
ð
G E N O F F D E L A Y
6 0 m i n
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
G E N O F F D E L A Y
0 6 0 m i n
4.4.2.19 ABSORP TIME
(Table 4.1, Parameter Setup Screen No. 19)
Parameter “ABSORP TIME” is used to set the time the charger will remain in Absorption Stage when the following
options for programming parameter “Charging Profile”
(See Section 4.4.2.21)
are selected:
• 1=3 Stage Type 1
• 3=2 Stage Type 1