44 | SAMLEX AMERICA INC.
APPENDIX A
SECTION 4 |
Parameter Setup
3
2=3Stage Type2
1.
Stage 1 – Bulk Stage
(See Section 5.7.1.1 of the attached EVO-
2212/3012/2224/4024 Manual for details):
• Charge at constant current = the programmed value of parameter “BULK
CURRENT”
(Default value is 40A.
For details of programming range & procedure, refer to Section 4.4.2.1
• Transition to Absorption Stage when voltage rises to the set value for programming
parameter “ABSORP VOLTAGE”
(
Default value is 14.4V for EVO-2212/3012 and 28.8V for EVO-
2224/4024.
For details of programming range & procedure, refer to Section 4.4.2.2
2.
Stage 2 - Absorption Stage
(See Section 5.7.2 of the attached EVO-
2212/3012/2224/4024 Manual for details ):
• Charge at constant voltage = the programmed value for parameter “ABSORP
VOLTAGE”.
(
Default value is 14.4V for EVO-2212/3012 and 28.8V for EVO-2224/4024.
For details of
programming range & procedure, refer to Section 4.4.2.2)
• Remain in Absorption Stage till the current reduces to value = the programmed
value of parameter “ABSORP EXIT AMPS”
(
Default value is 4A.
For details of programming
range & procedure, refer to Section 4.4.2.20)
• Transition to Float Stage thereafter.
3.
Stage 3 - Float Stage
(See Section 5.7.3 of the attached EVO-
2212/3012/2224/4024 Manual for details):
• Charge at constant voltage = the programmed value of parameter “FLOATING
VOLTAGE”.
(
Default value is 13.5V for EVO-2212/3012 & 27.0V for EVO-2224/4024.
For details of
programming range & procedure, refer to Section 4.4.2.4 )
• Reset to Bulk Stage under the following conditions:
i. If the AC input fails or is switched off and is restored subsequently.
ii. If battery voltage falls to the programmed value of parameter "RESET TO
BULK".
(Default value is 12.0V for EVO-2212/3012 & 24.0V for EVO-2224/4024
.
For details of
programming range & procedure, refer to Section 4.4.2.15).
iii. If the charger remains in the Float Stage for 10 days
− Lead Acid: Flooded
and Sealed – AGM/
Gel Cell
− Lithium
(See
Section 5.11 EVO-
2212/3012/2224/4024
Manual for details)
4
3=2Stage Type1
1.
Stage 1 – Bulk Stage
(See Section 5.7.1.1 of the attached EVO-
2212/3012/2224/4024 Manual for details):
• Charge at constant current = the programmed value of parameter “BULK
CURRENT”
(Default value is 40A.
For details of programming range & procedure, refer to Section 4.4.2.1
• Transition to Absorption Stage when voltage rises to the set value for programming
parameter “ABSORP VOLTAGE”
(
Default value is 14.4V for EVO-2212/3012 and 28.8V for EVO-
2224/4024.
For details of programming range & procedure, refer to Section 4.4.2.2
2.
Stage 2 - Absorption Stage
(See Section 5.7.2 of the attached EVO-
2212/3012/2224/4024 Manual for details ):
• Charge at constant voltage = the programmed value for parameter “ABSORP
VOLTAGE”.
(
Default value is 14.4V for EVO-2212/3012 and 28.8V for EVO-2224/4024.
For details of
programming range & procedure, refer to Section 4.4.2.2)
• Remain in Absorption Stage till the time in Absorption Stage is = the programmed
value of parameter “ABSORP TIME”
(
Default value is 60 min.
For details of programming range
& procedure, refer to Section 4.4.2.19)
• Switch off charging after expiry of programmed value of parameter “ABSORP TIME”
(
Default value is 60 min.
For details of programming range & procedure, refer to Section 4.4.2.19)
• Reset to Bulk Stage under the following conditions:
i. If the AC input from the Grid/Generator is disconnected and is reconnected.
ii. If battery voltage falls to the programmed value of parameter "RESET TO
BULK" .
(Default value is 12.0V for EVO-2212/3012 & 24.0V for EVO-2224/4024
.
For details of
programming range & procedure, refer to Section 4.4.2.15).
− Lithium (See Section
5.11 of EVO-
2212/3012/2224/4024
Manual for details )
− Nickel Zinc
(See
Section 5.10 of EVO-
2212/3012/2224/4024
Manual for details)