SAMLEX AMERICA INC. | 45
APPENDIX A
5
4=2Stage Type2
1.
Stage 1 – Bulk Stage
(See Section 5.7.1.1 of the attached EVO-
2212/3012/2224/4024 Manual for details):
• Charge at constant current = the programmed value of parameter “BULK
CURRENT”
(Default value is 40A.
For details of programming range & procedure, refer to Section 4.4.2.1
• Transition to Absorption Stage when voltage rises to the set value for programming
parameter “ABSORP VOLTAGE”
(
Default value is 14.4V for EVO-2212/3012 and 28.8V for EVO-
2224/4024.
For details of programming range & procedure, refer to Section 4.4.2.2
2.
Stage 2 - Absorption Stage
(See Section 5.7.2 of the attached EVO-
2212/3012/2224/4024 Manual for details ):
• Charge at constant voltage = the programmed value for parameter “ABSORP
VOLTAGE”.
(
Default value is 14.4V for EVO-2212/3012 and 28.8V for EVO-2224/4024.
For details of
programming range & procedure, refer to Section 4.4.2.2)
• Remain in Absorption Stage
• Reset to Bulk Stage under the following conditions:
i. If the AC input fails or is switched off and is restored subsequently
ii. If battery voltage falls to the programmed value of parameter "RESET TO
BULK" .
(Default value is 12.0V for EVO-2212/3012 & 24.0V for EVO-2224/4024
.
For details of
programming range & procedure, refer to Section 4.4.2.15).
− Lithium
(See Section
5.11 of EVO-
2212/3012/2224/4024
Manual for details)
6
5=2Stage Type3
1.
Stage 1 – Bulk Stage
(See Section 5.7.1.1 of the attached EVO-
2212/3012/2224/4024 Manual for details):
• Charge at constant current = the programmed value of parameter “BULK
CURRENT”
(Default value is 40A.
For details of programming range & procedure, refer to Section 4.4.2.1
• Transition to Absorption Stage when voltage rises to the set value for programming
parameter “ABSORP VOLTAGE”
(
Default value is 14.4V for EVO-2212/3012 and 28.8V for EVO-
2224/4024.
For details of programming range & procedure, refer to Section 4.4.2.2
2.
Stage 2 - Absorption Stage
(See Section 5.7.2 of the attached EVO-
2212/3012/2224/4024 Manual for details ):
• Charge at constant voltage = the programmed value for parameter “ABSORP
VOLTAGE”.
(
Default value is 14.4V for EVO-2212/3012 and 28.8V for EVO-2224/4024.
For details of
programming range & procedure, refer to Section 4.4.2.2)
• Remain in Absorption Stage till the current reduces to value = the programmed
value of parameter “ABSORP EXIT AMPS”
(
Default value is 4A.
For details of programming
range & procedure, refer to Section 4.4.2.20)
• Switch off charging after the current reduces to value = the programmed value of
parameter “ABSORP EXIT AMPS”
(
Default value is 4A.
For details of programming range &
procedure, refer to Section 4.4.2.20)
• Reset to Bulk Stage under the following conditions:
i. If the AC input fails or is switched off and is restored subsequently
ii. If battery voltage falls to the programmed value of parameter "RESET TO
BULK" .
(Default value is 12.0V for EVO-2212/3012 & 24.0V for EVO-2224/4024
.
For details of
programming range & procedure, refer to Section 4.4.2.15).
− Lithium
(See Section
5.11 of EVO-
2212/3012/2224/4024
Manual for details)
− Nickel Zinc (
See
Section 5.10 of EVO-
2212/3012/2224/4024
Manual for details)
4.4.2.21.1 Programming Steps for Parameter “CHARGING PROFILE”
Enter Key Enter Key Up Key x 20 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
B U L K C U R R E N T
4 0 A
ð
C H A R G I N G P R O F I L E
0 = 3 S t g A d a p t i v
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
C H A R G I N G P R O F I L E
0 = 3 S t g A d a p t i v
4.4.2.22 BATTERY TYPE
(Table 4.1, Parameter Setup Screen No. 22)
4.4.2.22.1 General Information
Parameter “BATTERY TYPE” is used to change the functionality of RJ-45 Jack marked “Battery Temp. Sensor” on the
front panel of EVO
[6, Fig 2.1 in EVO-2212/3012/2224/4024 Owner’s Manual]
. The following 2 programming options
are available:
SECTION 4 |
Parameter Setup