SAMLEX AMERICA INC. | 59
APPENDIX A
4.7 GROUP 4 PARAMETER SET UP: INPUT HIGH LIMIT
4.7.1 Programming Ranges and Default/ Factory Preset Values of Parameters Under Group 4 –
INPUT HIGH LIMIT
Table 4.6 gives details of programming ranges and default values of parameters under Parameter Group 4 - INPUT HIGH
LIMIT.
Refer to Fig 4.1 under Section 4.1 for Menu Map for navigating through various parameters under this Group 4
.
TABLE 4.6 GROUP 4 PARAMETER SET UP: INPUT HIGH LIMIT
Parameter
Setup Screen
No. for
Parameter
Group No.4
(Fig 4.1)
Parameter
Setting range
Default value
EVO-
2212
EVO-
3012
EVO-
2224
EVO-
4024
EVO-
2212
EVO-
3012
EVO-
2224
EVO-
4024
1
RESET VOLTAGE
120.0 – 150.0V
125.0V
2
CUT OFF VOLT 1
120.0 – 150.0V
135.0V
3
DETECT TIME 1
0 – 2000 cycles
60 cycles
4
CUT OFF VOLT 2
120.0 – 150.0V
140.0V
5
DETECT TIME 2
0 – 2000 cycles
15 cycles
6
CUT OFF VOLT 3
120.0 – 150.0V
145.0V
7
DETECT TIME 3
0 – 2000 cycles
1 cycle
4.7.2 Description of Parameters Under Group 4 – INPUT HIGH LIMIT
i
INFO
The values shown under various screens are the Default Values for EVO-2212
4.7.2.1 RESET VOLTAGE
(Table 4.6, Parameter Setup Screen No.1)
This is the reset voltage at which the unit will revert to "Charging Mode" after it has switched over to "Inverting Mode"
due to input voltage falling to "CUT-OFF VOLT 1
(Section 4.7.2.2)
, or CUT-OFF VOLT 2
(Section 4.7.2.4)
, or CUT-OFF
VOLT3"
(Section 4.7.2.6)
.
4.7.2.1.1 Programming Steps for Parameter "RESET VOLTAGE"
Enter Key Up Key x 3 times Enter Key Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
S E L E C T G R O U P
I N P U T L OW L I M I T
ð
R E S E T V O L T A G E
1 2 5 . 0 V
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
R E S E T V O L T A G E
1 2 5 . 0 V
SECTION 4 |
Parameter Setup