62 | SAMLEX AMERICA INC.
APPENDIX A
4.8.2 Description of Parameters Under Group 5 – OTHER FUNCTION
i
INFO
The values shown under various screens are the Default Values for EVO-2212
4.8.2.1 POWER SAVING
(Table 4.7, Parameter Setup Screen No.1)
i
INFO
For more information on use and application of Power Save Functions,
please refer to Sections 4.8.3 & 4.8.4
in the attached "Evolution Series Inverter/ Charger Owner's Manual for Models EVO-2212/3012/2224/4024.
"
Parameter "POWER SAVING" is used to enable or disable Power Saving Mode when in "Inverting Mode".
4.8.2.1.1 Programming Steps for Parameter "POWER SAVING"
Enter Key Up Key x 4 times Enter Key Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
S E L E C T G R O U P
O T H E R F U N C T I O N
ð
P OW E R S A V I N G
0 = D i s a b l e
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
P OW E R S A V I N G
0 = D i s a b l e
4.8.2.2 ENTER POINT
(Table 4.7, Parameter Setup Screen No.2)
If the value of power drawn by AC load falls to the "ENTER POINT" value for 5 sec, the unit will enter "Power Save
Mode"
(Section 4.8.2.1)
.
4.8.2.2.1 Programming Steps for Parameter "ENTER POINT"
Enter Key Up Key x 4 times Enter Key Up Key x 1 time Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
S E L E C T G R O U P
O T H E R F U N C T I O N
ð
P OW E R S A V I N G
0 = D i s a b l e
ð
E N T E R P O I N T
6 W
EVO-2212, 2224 - 6W
EVO-3012, 4024 - 8W
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
E N T E R P O I N T
0 6 W
4.8.2.3 WAKE UP POINT
(Table 4.7, Parameter Setup Screen No.3)
If the unit is in "Power Save Mode"
(Section 4.8.2.1)
and the value of the AC power of the load rises to "WAKE UP
POINT", the unit will quit "Power Save Mode" and will start operating in full voltage "Inverting Mode".
4.8.2.3.1 Programming Steps for Parameter "WAKE UP POINT"
Enter Key Up Key x 4 times Enter Key Up Key x 2 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
S E L E C T G R O U P
O T H E R F U N C T I O N
ð
P OW E R S A V I N G
0 = D i s a b l e
ð
W A K E U P P O I N T
7 W
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
W A K E U P P O I N T
0 7 W
4.8.2.4 REMOTE SWITCH
(Table 4.7, Parameter Setup Screen No.4)
This parameter is used when ON/OFF control of EVO™ Inverter/Charger is desired through external 12 VDC signal
fed to terminals marked "Remote ON/OFF" on the Front Panel of EVO™ Inverter/Charger
(15, Fig 2.1 in the attached
Owner's Manual for EVO-2212/3012/2224/4024)
.
SECTION 4 |
Parameter Setup