SAMLEX AMERICA INC. | 67
APPENDIX A
4.8.2.5.2.3 Option 4= Generator 2
This option will start the Generator at “LOW VOLT ALARM”
(Section 4.4.2.8)
and stop the Generator after the desired
programmed value of run time of the Generator = “GEN ON TIME”
(Section 4.4.2.17)
counted from the time the Status
Relay is switched ON (energized).
Further details are given below:
• If the battery voltage drops to “LOW VOLT ALARM”
(Section 4.4.2.8)
, or lower for continuous period = “GS
DETECT TIME”
(Section 4.4.2.16)
, the Status Relay will be switched ON (energized). “Common” and “NO”
contacts of the Status Relay will close to initiate automatic starting of the Generator
• Once the generator has started and starts feeding AC output (within the programmed limits of voltage and
frequency), the EVO™ will change over from “Inverting Mode” to “Charging Mode”. Battery charging will be
initiated as per the charging profile set by parameter "CHARGING PROFILE"
(Section 4.4.2.21)
• The Status Relay will be switched OFF (de-energized) after expiry of the desired programmed Generator run
time = “GEN ON TIME”
(Section 4.4.2.17)
counted from the time the Status Relay is switched ON (energized).
“Common” and “NO” contacts of the Status Relay will open to initiate automatic stopping of the Generator.
When AC output from the Generator switches OFF, EVO™ will change over to “Inverting Mode”
(NOTE: The
State of Charge of the battery after the Status Relay has been switched OFF (de-energized) and Generator is
stopped will be indeterminate).
4.8.2.5.3 Programming Steps for Parameter "RELAY FUNCTION"
Enter Key Up Key x 4 times Enter Key Up Key x 4 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
S E L E C T G R O U P
O T H E R F U N C T I O N
ð
P OW E R S A V I N G
0 = D i s a b l e
ð
R E L A Y F U N C T I O N
2 = G e n e r a t o r 0
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
R E L A Y F U N C T I O N
2 = G e n e r a t o r 0
4.8.2.6 COMM ID
(Table 4.7, Parameter Setup Screen No.6)
Communication ID- This sets the ID number for the COMM Port and EVO-RC Remote Control.
4.8.2.6.1 Programming Steps for Parameter "COMM ID"
Enter Key Up Key x 4 times Enter Key Up Key x 5 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
S E L E C T G R O U P
O T H E R F U N C T I O N
ð
P OW E R S A V I N G
0 = D i s a b l e
ð
C O MM .
I D
1
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
C O MM .
I D
0 0 1
4.8.2.7 BUZZER
(Table 4.7, Parameter Setup Screen No.7)
Set the buzzer ON/OFF.
4.8.2.7.1 Programming Steps for Parameter "BUZZER"
Enter Key Up Key x 4 times Enter Key Up Key x 6 times Enter Key
A N Y O P E R A T I N G
M O D E S C R E E N
ð
S E L E C T G R O U P
C H A R G E C U R V E
ð
S E L E C T G R O U P
O T H E R F U N C T I O N
ð
P OW E R S A V I N G
0 = D i s a b l e
ð
B U Z Z E R
1 = O n
ð
K E Y I N P A S S WO R D
0 0 0 0
Password 8052
See Section 4.3.1
ð
B U Z Z E R
1 = O n
SECTION 4 |
Parameter Setup