SAMLEX AMERICA INC. | 71
APPENDIX A
Date
Time
Gen
status
Gen
freq
Gen
volt
Grid
status
Grid
freq
Grid
volt
Input
current
Input
VA
Inputt
watt
Output
freq
Output
Volt
Output
current
Output
VA
Output
watt
Battery
volt
Battery
current
External
current
Battery
temperature
Transformer
temperature
Busbar
temperature
Heat sink
temperature
Fan
speed
Mode
Error
Code
Charge
stage
Event
Fig 5.1 Data Logging Fields
The Data Fields shown in Fig 5.1 above can be recorded at one of the 6 time interval options shown below under
programming parameter “DATALOG TIME”
(See Section 4.8.2.10)
.
Default time interval is 1 sec
(Option “1=1 sec).
Parameter “DATALOG TIME” is also used to disable data logging (Option 0=Disable)
. Interval / disabling options are
shown below:
• 0 = Disable ; 1 = 1 sec (Default) ; 2 = 10 sec ; 3 = 30 sec ; 4 = 60 sec ; 5 = 5 min ; 6 = 10 min
NOTE
The last data field “Event” shown in Fig 5.1 above records an event as soon as it occurs
5.2.2 Operating Screens when SD Card is Inserted for Data Logging
Data logging will be carried out automatically
as soon as the SD Card is inserted in the SD Card Slot of EVO-RC.
[Provided parameter “DATALOG TIME” (Section 4.8.2.10) has NOT been set to “0 = Disable”)]
.
Operating screens are shown below:
F I L E C R E A T I N G . . .
Data log function has been initiated and new file is being created.
Do not remove the SD card when file creating is displayed.
S D C A R D
R E A D E R R O R !
Read error, the data log function/ update/ upload will stop.
S D C A R D
W R I T E E R R O R !
Write error. The Data logging function will stop.
S D C A R D F U L L !
There is not enough space to create Data Log File Folder or to
save file with saved programmed parameters.
NOTE: Once there is enough space to create a Data Log
File Folder and subsequently, it runs out of capacity due to
recording newer data, it will start to overwrite on older files.
5.2.3 Disabling Data Logging
In the factory default condition, data logging has been
enabled
at 1 sec recording interval
[Parameter “DATALOG
TIME” (Section 4.8.2.10) has been set to option “1 = 1 sec”]
.
Hence, data logging will commence as soon as SD Card
is inserted.
To
disable data logging
, parameter “DATALOG TIME”
(Section 4.8.2.10)
has to be set at option “0 = Disable”.
SECTION 5 |
SD Card