SAMLEX AMERICA INC. | 9
APPENDIX A
3.3 DATE AND TIME SETUP
Set date and time as per procedure given at Section 4.9: “Group 6 Parameter Setup: Time Setting”.
3.4 STANDBY MODE
When the EVO™ is in Standby Mode, inverting or charging / AC pass through will be suspended.
i
INFO
Standby Mode may be used to temporary halt normal operation of the Inverter/Charger without switching
OFF the unit completely.
For the Standby Mode to be switched ON, the EVO™ should be in ON condition and should be operating in one of the
4 Operating Modes – “Inverting” or “Charging”, “Power Saving” or "Online" (See Fig 3.2). When Standby Mode is
switched ON, the EVO™ will suspend its Operating Mode.
3.4.1 Procedure to Enter and Exit Standby Mode / Status Display in Standby Mode
i
INFO
• EVO-RC Remote Control will be required to be connected to the EVO Inverter-Charger Unit to enter
Standby Mode as explained at Section 3.4.1.1 below. Once Standby Mode has been entered using EVO-RC
Remote Control, it can
ALSO
be switched off using the On/Off Push Button on the front panel of the EVO
Inverter-Charger Unit (See Section 3.4.1.2)
•
If EVO-RC Remote Control has
NOT
been connected to the EVO Inverter-Charger Unit, Standby Mode
cannot be entered using the On/Off Push Button on the front panel of the EVO Inverter-Charger Unit
3.4.1.1 Entering Standby Mode Using Remote Control EVO-RC:
Changing over from any Operating
Mode (“Inverting”, “Charging” or “Power Save”) to Standby Mode can be carried out with the help of
Remote-Control EVO-RC as follows:
a) From any Operating Mode Screen (“Inverting”, “Charging” or “Power Save”), press the On/Off Push Key (2, Fig
1.1) momentarily (0.1 sec)
b) Screen 1 below will be displayed first for 1 sec followed by Screen 2 below for 1 sec.
This display sequence will
be displayed 2 times and then, the screen will go back to the Operating Mode Screen.
•
If Standby Mode is required to be activated, press the On/Off Push Key
(2, Fig 1.1)
momentarily
(0.1 sec)
•
If Standby Mode is not required to be activated, press the Back Key
(5, Fig 1.1)
momentarily
(0.1 sec)
Screen
1:
Screen 2:
G o t o S t a n d b y ?
Y e s = O n / O f f k e y
G o t o S t a n d b y ?
N o = B a c k k e y
SECTION 3 |
Operation