46 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 47
SECTION 8 |
Installation
• Press the “Reset Button” (5A in Fig 6.1). The GFCI will reset and AC power to the load
side outlets will be restored. Status LED (5C in Fig 6.1) will turn Green. The test lamp
will also switch ON.
• If the above Test / Reset operation cannot be carried out, replace the GFCI.
8.5.2.3 GFCI Tripping and Reset: If there is a leakage of 5 to 6mA due to ground fault
on the load side or , there is a Neutral to Ground bond on the load side, the GFCI will trip
and the “Reset Button” (5A in Figs 6.1) will pop out. AC power to the load side outlets will
be cut off. Status LED (5C in Figs 6.1) will switch OFF. Remove the ground fault in the load
circuit. Press the “Reset Button” (5A in Fig 6.1). The GFCI will reset and AC power to the
load side outlets will be restored. Status LED (5C in Figs 6.1) will turn Green.
i
INFO
For the Reset Button (5A, Fig 6.1) to operate, the Inverter has to be in ON
condition so that AC power is available to the internal Line Side of the GFCI.
!
CAUTION!
1. Do not feed the output from the GFCI receptacle to a Panel Board / Load Center
where the Neutral is bonded to the Earth Ground. This will trip the GFCI.
2. If an extension cord is used, please ensure that the cord is 2-Pole Grounding Type
(3 pin).
!
ATTENTION!
1. N'alimentent pas la sortie de la prise GFCI à un Panel de sélection / Charger
Centre où la position neutre est lié à la terre. Ce qui déclenche le disjoncteur.
2. Si une rallonge est utilisée, veuillez vous assurer que le cordon est mise à la
terre à 2 pôles (3 broches).
8.6 PROVIDING BACKUP POWER USING TRANSFER SWITCH
For this application, use a Transfer Switch that has Double Pole, Double Throw Contacts
like in Samlex America, Inc. Transfer Switch Model No. STS-30. This type of Transfer
Switch will be able to switch both the Hot and the Neutral and will prevent tripping of
the GFCI due to Neutral to Ground bond in the Utility power (See Section 8.5.2.3):
- Feed utility power and output power from the inverter to the two inputs of the Trans-
fer Relay
- Feed the output of the Transfer Switch to a Sub-Panel to feed AC loads requiring
backup power
- Do not bond (connect) the Neutral and the Ground in the Sub-Panel
- When Utility power is available, the 2 poles of the Transfer Switch will connect the