54 | SAMLEX AMERICA INC.
10. PROTECTIONS
The inverter has been provided with protections detailed below:
10.1 POWER SURGE / OVERLOAD / SHORT CIRCUIT PROTECTIONS
i
INFO
Please refer to definitions of Active Power (Watts, W), Apparent Power (VA)
and Power Factor (PF) at Section 2.1. In the explanation below, the values of
Power are expressed in Apparent Power (VA). Corresponding Active Power
(Watts, W) will depend upon the type of load (Resistive or Reactive) and it’s
Power Factor, (PF) (The value of PF may range from 1 to 0.5). Please note the fol-
lowing:
• Active Power (Watts, W) = Apparent Power (VA) x Power Factor (PF).
• For resistive type of loads, the Power Factor (PF) = 1 and hence, Apparent
Power (VA) = Active Power (Watts, W)
• For reactive types of loads, the Power Factor (PF) will be < 1 (up to 0.5) and
hence, the Active Power (Watts, W) will be less than the Apparent Power (VA)
i
INFO
Veuillez vous reporter aux définitions de la puissance active (Watts, W), la
puissance apparente (VA) et le facteur de puissance (PF) à la section 2.1.
Dans l'explication ci-dessous, les valeurs de puissance sont exprimées dans
la puissance apparente (VA). Puissance active correspondante (Watts, W)
dépendra du type de charge (charge résistive ou réactif) et c'est le facteur de
puissance (facteur de puissance peut aller de 1 à 0,5). Veuillez noter ce qui suit :
• Puissance active (W) = Puissance apparente (VA) x Facteur de puissance (PF).
• Pour les charges de type résistif, le facteur de puissance = 1 et par
conséquent, la puissance apparente (VA) = Puissance active (Watts, W)
• Pour les types de charges, le facteur de puissance sera < 1 (jusqu'à 0,5) et par con-
séquent, la puissance active (Watts, W) est inférieure à la puissance apparente (VA)
10.1.1 Surge Power Rating: "Surge Power Rating" of an inverter indicates its short term
overload capability i.e. its capability to provide higher than its rated continuous power
for a very short duration to enable starting of certain types of devices/ appliances like
electric motor driven pumps, compressors etc. that require higher starting power than
their rated continuous running power. More examples of such types of devices/ appliances
are given at Section 2.5, Table 2.1.
Surge Power ratings of PST-600-12/ PST-600-24 is 1000W (166% of its rated continuous
power of 600W) for < 1 sec.
If the AC load continues to draw power equal to the above surge power/ short-term over-
load limits, the inverter will shut down due to overload / short circuit protection described
at Sections 10.1.2 and 10.1.3 below.
SECTION 10 |
Protections