EB 8052-E EN
5-3
Installation
pressure rating of the pipeline, medium
temperature etc.). See the 'Markings on
the device' section for nameplate details.
− The requested or required additional
pipe fittings (see the 'Additional fittings'
section) have been installed or prepared
as necessary before installing the valve.
Risk of control valve damage due to
incorrect insulation.
Î
Do not insulate valves mounted to com-
ply with NACE MR0175 requirements
and which have nuts and bolts that are
not suitable for sour gas environments.
Proceed as follows:
Î
Lay out the necessary material and tools
to have them ready during installation
work.
Î
Flush the pipelines.
The plant operator is responsible for clean-
ing the pipelines in the plant.
Î
For steam applications, dry the pipelines.
Moisture will damage the inside of the
valve.
Î
Check any mounted pressure gauges to
make sure they function properly.
Î
When the valve and actuator are al-
ready assembled, check the tightening
torques of the bolted joints (
u
Components may loosen during trans-
port.
5.3 Mounting the device
The activities listed below are necessary to
install the valve and before it can be started
up.
Risk of valve damage due to excessively
high or low tightening torques.
Observe the specified torques when tighten-
ing control valve components. Excessive
tightening torques lead to parts wearing out
more quickly. Parts that are too loose may
cause leakage.
Î
Observe the specified tightening torques
(
u
Risk of valve damage due to the use of
unsuitable tools.
Î
Only use tools approved by SAMSON
(
u
NOTICE
!
Note
NOTICE
!
NOTICE
!
Summary of Contents for 3251-E
Page 6: ...Contents EB 8052 E EN ...
Page 34: ...4 6 EB 8052 E EN ...
Page 86: ...9 28 EB 8052 E EN Servicing and conversion ...
Page 92: ...12 2 EB 8052 E EN ...
Page 94: ...13 2 EB 8052 E EN ...
Page 96: ...14 2 EB 8052 E EN ...
Page 100: ...15 4 EB 8052 E EN ...
Page 101: ......