EB 8332-2 EN
16-7
Annex A (configuration instructions)
−
Next entry in information level (c11 = NEXT):
If the
NEXT
function is selected in Code
c11, the first code of the information level (i01) is displayed as soon as binary input
switching state is changed. After every new change to the active state, the next code of
the information level appears (i02, i03 etc.). The display returns to the start screen after
all the codes of the information level have been displayed due to the binary input switch-
ing or when the binary input's switching state remains unchanged for five minutes.
−
Backlight (c11 = LAMP):
When the binary input's switching state is active, the display
backlight is switched on permanently.
−
Exit manual level for travel adjustment (c11 = MEND):
When the binary input's switch-
ing state is active, the actuator exits the manual mode. The actuator stem moves to the
valve position determined by the automatic mode.
Code
Description
WE
Adjustment range
c11
Function
NONE
NONE (inactive)
PRIO (priority position)
NEXT (next entry in information level)
LAMP (backlight activated)
MEND (exit manual level for travel
adjustment)
c12
Switching state for active function
NINV
NINV (not inverted)
INV (inverted)
When c11 = PRIO:
c34
Travel for priority position
0.0 %
0.0 to 100.0 %
16.7 Binary output
The binary output is a floating contact. The function and switching state of the binary input
can be configured as required.
−
Inactive (c15 = NONE):
No function is assigned to the binary output.
−
Error indication (c15 = FAIL):
when an error ( icon) is registered, the error message is
issued at the binary output.
−
Limit contact (c15 = LIM):
the binary output is used as an electronic limit contact (see sec-
tion 16.8). To configure this function, the required settings must be made in Codes c21 to
c23. The use of the binary output as an electronic limit contact is independent from the
optionally installed electronic limit contacts.
−
Priority position (c15 = PRIO):
When the priority position function is active (
c11 = PRIO
),
this is registered at the binary output after the actuator stem stops moving.
Summary of Contents for 3375
Page 6: ...Contents EB 8332 2 EN ...
Page 12: ...1 6 EB 8332 2 EN ...
Page 40: ...5 16 EB 8332 2 EN ...
Page 45: ...EB 8332 2 EN 6 5 Operation Fig 6 3 Housing cover of special version with three key operation ...
Page 46: ...6 6 EB 8332 2 EN ...
Page 63: ...EB 8332 2 EN 8 5 Setup 1 2 Fig 8 2 Manual override ...
Page 72: ...8 14 EB 8332 2 EN ...
Page 78: ...9 6 EB 8332 2 EN ...
Page 80: ...10 2 EB 8332 2 EN ...
Page 82: ...11 2 EB 8332 2 EN ...
Page 84: ...12 2 EB 8332 2 EN ...
Page 86: ...13 2 EB 8332 2 EN ...
Page 88: ...14 2 EB 8332 2 EN ...
Page 90: ...15 2 EB 8332 2 EN Certificates EU declaration of conformity ...
Page 122: ...16 32 EB 8332 2 EN ...
Page 125: ...EB 8332 2 EN 17 3 Service key number 1732 Customized key number ...
Page 126: ...17 4 EB 8332 2 EN ...
Page 127: ......
Page 128: ......
Page 129: ......