logger
parameter and select
Execute
to start
data logging.
Permanent data logging
The variables w, x, y, and e are logged ac-
cording to the adjusted scan rate and saved
in the FIFO memory which always stores the
last 100 measured data points of each vari-
able.
Triggered data logging
On selecting
Trigger
in the
Selection
param-
eter, the data logger records the measured
data permanently in the background. A trig-
gering event leads to the last 100 measured
data points being stored together with the
pretrigger time and leads to the data log-
ging of the triggering condition.
The following parameters can be changed
for this function:
4
Trigger status:
Triggered by the travel condition
(setpoint) and/or solenoid valve condi-
tion (forced venting)
4
Start value:
Limit indicating from which travel condi-
tion (setpoint) the data logger should be
triggered
4
Logging limit:
Indicating whether data logging should
start when the travel condition (setpoint)
exceeds or falls below the start value.
Travel condition (setpoint)
Note!
The valve position is used as the travel
condition in positioners in ESD version.
Select
Trigger status
parameter and select
Start trigger via travel condition (setpoint)
.
Activate data logging by selecting
Start data
10
EB 8388 EN
Statistical information AUTO
Fig. 3 · Data logger