26
EB 8384-0 EN
Attachment to the control valve – Mounting parts and accessories
4.4
Attachment to Type 3510
Micro-flow Valve
The positioner is attached to the valve yoke
using a bracket.
Refer to Table 5 on page 33 for the re
-
quired mounting parts and accessories listed
with their order numbers.
Refer to travel table on page 13.
1.
Screw bracket (9.1) to the stem connector
(9).
2.
Fasten the two pins (9.2) to the bracket
(9.1) on the stem connector. Mount the
follower plate (3) and fasten it using the
screws (9.3).
3.
Mount the travel indication scale (acces
-
sories) to the outer side of the yoke using
the hex screws (12.1), ensuring that the
scale is aligned with the stem connector.
4.
Fasten the hex bar (11) onto the outer
side of yoke by screwing the M8 screws
(11.1) directly into the holes on the yoke.
5.
Fasten the bracket (10) to the hex bar
(11) using the hex screw (10.1), washer
and tooth lock washer.
6.
Mount connecting plate (6) or pressure
gauge bracket (7) with pressure gauges
(8) on the positioner, making sure both
seal rings (6.1) are seated properly.
7.
Unscrew the standard installed lever M
(1) including follower pin (2) from the
positioner shaft.
8.
Take lever S (1) and screw follower pin
(2) in the bore for pin position 17.
9. Place lever S on the positioner shaft and
screw tight using the disk spring (1.2)
and nut (1.1).
Move lever once all the way as far as it
will go in both directions.
10.
Place positioner on the bracket (10) in
such a manner that the follower pin
slides into the groove of the clamp (3).
Adjust the lever (1) correspondingly.
Screw the positioner to the bracket (10)
using both its screws.
4.5
Reversing amplifier for
double-acting actuators
For the use with double-acting actuators, the
positioner must be fitted with a reversing am
-
plifier, e.g. the SAMSON Type 3710 Revers
-
ing Amplifier (see Mounting and Operating
Instructions
u
EB 8392 EN).
If a different reversing amplifier (item no.
1079-1118 or 1079-1119) is used, follow
the mounting instructions described in sec
-
tion 4.5.1.
The following applies to all reversing am
-
plifiers:
The signal pressure of the positioner is sup
-
plied at the output
A
1
of the reversing ampli
-
fier. An opposing pressure, which equals the
required supply pressure when added to the
pressure at
A
1
, is applied at output
A
2
.
Summary of Contents for 3730-0
Page 11: ...EB 8384 0 EN 11 ...
Page 47: ...EB 8384 0 EN 47 ...
Page 48: ...48 EB 8384 0 EN ...
Page 49: ...EB 8384 0 EN 49 ...
Page 50: ...50 EB 8384 0 EN ...
Page 51: ...EB 8384 0 EN 51 ...
Page 52: ...52 EB 8384 0 EN ...
Page 53: ...EB 8384 0 EN 53 ...
Page 54: ...54 EB 8384 0 EN ...
Page 55: ...EB 8384 0 EN 55 ...
Page 56: ...56 EB 8384 0 EN ...
Page 57: ...EB 8384 0 EN 57 ...
Page 62: ...62 EB 8384 0 EN ...
Page 63: ...EB 8384 0 EN 63 ...