EB 8384-0 EN
9
Design and principle of operation
Type 3730-0 Positioner (the technical data for explosion-protected devices may be restricted by the limits
specified in the test certificates)
Characteristic
Linear, deviation from characteristic ≤ 1 %
Hysteresis
≤ 1 %
Sensitivity
≤ 0.1 %
Direction of action
Selectable over DIP switch
Air consumption, steady state
Independent from supply pressure approx. 120 l
n
/h
Air output capacity
Actuator filled with air
Actuator vented
When Δp =6 bar: 8.5 m
n
³/h, when Δp = 1.4 bar: 3.0 m
n
³/h K
Vmax(20 °C)
= 0.09
When Δp =6 bar: 14.0 m
n
³/h, when Δp = 1.4 bar: 4.5 m
n
³/h K
Vmax(20 °C)
= 0.15
Permissible ambient temperature –20 to +80 °C
–45 to +80 °C with metal cable gland
The temperature limits for explosion-protected devices may be restricted by the
limits specified in the test certificates.
Influences
Temperature: ≤ 0.15 %/10 K
Supply air: None
Vibrations: ≤ 0.25 % up to 2000 Hz and 4 g according to IEC 770
Electromagnetic compatibility
Complying with EN 61000-6-2, EN 61000-6-3, EN 61326-1 and NAMUR Rec
-
ommendation NE 21
Use in safety-instrumented
systems acc. to IEC 61508
Suitable for use in safety-instrumented systems up to SIL 2 (single device) and SIL 3
(with redundant configuration), emergency shutdown at a reference variable of
0 mA
Degree of protection
IP 66
Materials
Die-cast aluminum EN AC-Al Si12(Fe) (EN AC-44300) acc. to DIN EN 1706,
chromated and plastic coated
External parts: stainless steel 1.4404/316L
Weight
Approx. 1 kg
Compliance
·
Summary of Contents for 3730-0
Page 11: ...EB 8384 0 EN 11 ...
Page 47: ...EB 8384 0 EN 47 ...
Page 48: ...48 EB 8384 0 EN ...
Page 49: ...EB 8384 0 EN 49 ...
Page 50: ...50 EB 8384 0 EN ...
Page 51: ...EB 8384 0 EN 51 ...
Page 52: ...52 EB 8384 0 EN ...
Page 53: ...EB 8384 0 EN 53 ...
Page 54: ...54 EB 8384 0 EN ...
Page 55: ...EB 8384 0 EN 55 ...
Page 56: ...56 EB 8384 0 EN ...
Page 57: ...EB 8384 0 EN 57 ...
Page 62: ...62 EB 8384 0 EN ...
Page 63: ...EB 8384 0 EN 63 ...