background image

18

EB 8388-1 EN

ESD functions

Code

No.

Parameters – display

,

Values [default settings]

Description

49

ESD error codes (display only)

F0 No test available

No test available or test cancelled manually

F1 Test OK
F2 x cancellation

Test cancelled by the x cancellation function

F3 y cancellation

Test cancelled by the y cancellation function

F4 Tolerance band exceeded

The test has been cancelled. x values outside the toler-
ance band occurred

F5 Max. test time exceeded

Test not completed within the maximum test
duration and therefore cancelled

F6 Test manually cancelled

Test cancelled by the operator

F7 Measured data storage out of

memory

Storage for measured values out of memory. After 100
measured values per measured variable, the logging is
stopped. However, the test is still continued.

F8 Aborted by solenoid valve

Test cancelled by the solenoid valve being triggered

F9 Supply pressure/ friction

Test cancelled due to insufficient supply pressure or
excessive friction

Summary of Contents for 3730-3 ESD

Page 1: ...ectropneumatic Positioner Type 3730 3 ESD Version With HART communication Mounting and Operating Instructions EB 8388 1 EN Firmware version 1 4x Edition November 2006 Fig 1 ESD mode in SAMSON TROVIS V...

Page 2: ...ting the diagnostic ESD log 7 2 ESD functions 8 2 1 Changing ESD parameters and starting the partial stroke test 12 2 1 1 On site operation 13 2 2 Analyzing measured data 13 2 2 1 Condensed state Faul...

Page 3: ...s active the positioner keeps the attached valve to a set position e g open The valve does not per form any control tasks anymore In AUTO operating mode the positioner can be used to control the attac...

Page 4: ...ording to sched ule ESD Auto Partial stroke test The partial stroke test integrated into the positioner can prevent a normally open valve or a valve in its end position from seizing up or getting jamm...

Page 5: ...ositioner 1 3 1 Converting TROVIS VIEW 3 The TROVIS VIEW 3 version must match the software version of the positioner When establishing communication or ex changing data between the PC and the position...

Page 6: ...ng mode The ESD code can be found on page 21 Remove the code or make it unreadable to prevent unauthorized use Entering the code on the positioner Default OFF Turn Code 3 Press Turn ON Press Display s...

Page 7: ...ion Select Print in the File menu to add further information 1 In the File menu select Print Options to choose the scope of the diagnostic log After installing updating the TROVIS VIEW software custom...

Page 8: ...SD mode parameter in the Diagnosis folder under Emergency Shut Down is set to On In ESD mode the safety shut off valve is specifically moved to the set point of the valve working range parameter Requi...

Page 9: ...before the test starts Starting from the Step start position pos 2 the valve moves to the defined end position Step end parameter pos 3 The valve re mains in this position for the time defined by the...

Page 10: ...ction Fig 2 right The ramp function is active when the Activa tion of the ramp function parameter is set to On Note A step before the partial stroke test can be prevented by allocating the value of th...

Page 11: ...e value falls below the adjusted valve position range 10 to 110 The condition is only active when Activa tion x control is set to On 4 y control value The test is cancelled when the value falls below...

Page 12: ...s ESd the Manual reference variable w and MAN 5 Set the parameters in the Emergency Shut Down folder as desired The further course of action depends on whether the test is to be started manually Test...

Page 13: ...when the positioner is in ESD Man operating mode 4 Setting the reference variable Manual w using Code 1 4 Setting the ESD parameters using Code 49 see section 2 5 Starting the partial stroke test 1 Se...

Page 14: ...ead time s 4 T63 s 4 T98 s 4 Rise time s 4 Settling time s 2 2 1 Condensed state Fault alarm output The Fault alarm output parameter allows you to define which type of alarm is issued by the hardware...

Page 15: ...easured values of the parame ters determined during the partial stroke test are listed in the Measured data folder 2 4 Resetting ESD TROVIS VIEW 3 Diagnosis Emergency Shut Down Reset ESD Using the Res...

Page 16: ...l angle is displayed in when the positioner is initialized Otherwise the sensor position in relation to the central axis is indicated in degrees 3 Unlocking the positioner configuration OFF ON ESC OFF...

Page 17: ...0 0 0 The test is cancelled when the valve position falls below this value E2 Activation y control On Off Off Activates or deactivates y monitoring Activation only makes sense when the partial stroke...

Page 18: ...led x values outside the toler ance band occurred F5 Max test time exceeded Test not completed within the maximum test duration and therefore cancelled F6 Test manually cancelled Test cancelled by the...

Page 19: ...no further settings need to be entered EB 8388 1 EN 19 EXPERT test functions Operating mode Code 0 EXPERT functions Test requirements AUtO As in EB 8388 EN MAN ESD mode ESD Man Data logger Statistica...

Page 20: ...the con trol system and the asset management sys tem As shown in Fig 4 no solenoid valve is re quired since the positioner similar to the so lenoid valve is certified for safe shutdown When the energy...

Page 21: ...tegrated into the positioner terminals 81 82 is used to gether with an existing external solenoid valve to trigger the data logger EB 8388 1 EN 21 Notes on applications ESD code 1732 24 V 4 20 mA 81 8...

Page 22: ...22 EB 8388 1 EN...

Page 23: ...EB 8388 1 EN 23...

Page 24: ...SAMSON AG MESS UND REGELTECHNIK Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 Internet http www samson de EB 8388 1 EN 2007 01...

Reviews: