3
EXPERT
+
test functions
By default, all positioners in ESD version in-
clude the EXPERT
+
valve diagnostic func-
tions. However, the positioner’s operating
mode determines which diagnostic functions
are available.
Presetting actuator and valve data
To use the integrated EXPERT
+
functions,
certain details on the actuator and valve
used need to be entered, including:
4
Model parameter under [Identification >
Positioner > Actuator]
Options: single acting, double acting
Default: single acting
4
Booster parameter under [Identification >
Positioner > Actuator]
Options: not present, present
Default: not present
4
Stuffing box parameter under [Identifica-
tion > Positioner > Valve]
Options: self-adjusting, adjustable pack-
ing, bellows seal
Default: self-adjusting
If actuator and valve correspond to the de-
fault values, no further settings need to be
entered.
EB 8388-1 EN
19
EXPERT
+
test functions
Operating mode
(Code 0)
EXPERT
+
functions
Test requirements
AUtO
As in EB 8388 EN
MAN
ESD mode
ESD Man
Data logger/ Statistical
information Auto
TROVIS-VIEW 3:
[Diag-
nosis > Statistical information
AUTO > Data logger]
For test description,
see
EB 8388 EN
, section 2.1
Note!
The valve position is used as the valve
travel condition by the data logger of
positioners in ESD version.
Drive signal y Hysteresis/
Statistical information Auto
TROVIS-VIEW 3:
[Diag-
nosis > Statistical information
AUTO > Drive signal dia-
gram > Hysteresis]
For test description and requirements, see
EB 8388 EN
, section 2.5.2
Actuator and valve data need to be preset, see
above
ESD Auto
Data logger/ Statistical
information Auto
TROVIS-VIEW 3:
[Diag-
nosis > Statistical information
AUTO > Data logger]
For test description,
see
EB 8388 EN
, section 2.1
Note!
The valve position is used as the valve
travel condition by the data logger of
positioners in ESD version.