Code
no.
Parameter
– Display, values
[default setting]
Description
Important
! Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
7*
w/x
[
ää
] increasing/increasing
äæ
increasing/decreasing
ESC
Direction of action of the reference variable w in relation to the
travel/angle of rotation x
Automatic adaptation:
AIR TO OPEN:
On completing initialization, the direction of action remains in-
creasing/increasing (
ää
), a globe valve opens as the mA signal
increases.
AIR TO CLOSE:
On completing initialization, the direction of action changes to
increasing/decreasing (
äæ
), a globe valve closes as the mA
signal increases.
8*
Lower x-range value
0.0 to 80.0 [0.0] % of the
nominal range
ESC
Note:
Specified in mm or
angle ° provided Code 4 is
set
Lower range value for the travel/angle of rotation in the nominal
or operating range.
The
operating range
is the actual travel/angle of the control
valve and is limited by the lower x-range value (Code 8) and the
upper x-range value (Code 9).
Usually, the operating range and the nominal range are identi-
cal. The nominal range can be limited to the operating range by
the lower and upper x-range values.
Value is displayed or must be entered.
The characteristic is adapted. See also the example in Code 9!
9*
Upper x-range value
20.0 to 100.0 [100.0] % of
the nominal range
ESC
Note:
Specified in mm or
angle ° provided Code 4 is
set
Upper range value for the travel/angle of rotation in the nominal
or operating range.
Value is displayed or must be entered.
The characteristic is adapted.
Example: The operating range is modified, for example, to limit
the range of a control valve which has been sized too large. For
this function, the entire resolution range of the reference variable
is converted to the new limits. 0 % on the display corresponds to
the adjusted lower limit and 100 % to the adjusted upper limit.
10* Lower x-limit
0.0 to 49.9 % of the
operating range
[OFF], ESC
Limitation of the travel/angle of rotation downwards to the en-
tered value, the characteristic is not adapted.
The characteristic is not adapted to the reduced range. See also
example in Code 11.
EB 8384-4 EN
113
Appendix
Summary of Contents for 3730-4
Page 2: ...2 EB 8384 4 EN...
Page 127: ......
Page 188: ...188 EB 8384 4 EN...
Page 189: ...EB 8384 4 EN 189...
Page 190: ...190 EB 8384 4 EN...
Page 191: ...EB 8384 4 EN 191...
Page 192: ...192 EB 8384 4 EN...
Page 193: ...EB 8384 4 EN 193...
Page 194: ...194 EB 8384 4 EN...
Page 195: ...EB 8384 4 EN 195...
Page 196: ...196 EB 8384 4 EN...
Page 197: ...EB 8384 4 EN 197...
Page 198: ...198 EB 8384 4 EN...
Page 199: ...EB 8384 4 EN 199...
Page 206: ...206 EB 8384 4 EN...
Page 207: ...EB 8384 4 EN 207...
Page 208: ...208 EB 8384 4 EN...
Page 209: ...EB 8384 4 EN 209...
Page 210: ...210 EB 8384 4 EN...
Page 211: ...EB 8384 4 EN 211...