164
EB 8384-4 EN
Appendix
AO Transducer Block, Slot 1 · Profile-specific parameters
Parameter
Index
SK
Access
Mode
Selection/display [default value]
Description
SELF_CALIB_STATUS
114
r
[0]
Manufacturer-specific status of the sequence started with SELF_CALIB_CMD parameter
Note:
0 = Undetermined
1 = In progress
2 = Canceled
3 = Range incorrect
4 = Error in mechanics/pneumatics
5 = Gain error
6 = Offset error
7 = Calibration sequence mixed up
11 = Time out
12 = Proportional range restricted too much
13 = Rated travel or transmission incorrectly
14 = Mechanics system stuck (during initialization)
15 = Pneumatics system leaks (during initialization)
16 = Action interrupted as a production test has not
17 = Initialization status: Mechanical stops
SERVO_GAIN_1
115
S
r/w
ALL
[7]
K
SERVO_RATE_1
116
S
r/w
ALL
[2]
T
SETP_CUTOFF_DEC
118
S
r/w
ALL
[0.0 %]
Final position w < (Code 14)
If the reference variable exceeds the entered value, the valve moves towards the final position which corresponds
to 0 % reference variable.
Electropneumatic actuators are completely filled with air or vented (depending on the fail-safe position).
SETP_CUTOFF_INC
119
S
r/w
ALL
[125.0 %]
Final position w > (Code 15)
If the reference variable exceeds the entered value, the valve moves towards the final position which corresponds
to 100 % reference variable.
Electropneumatic actuators are completely filled with air or vented (depending on the fail-safe position).
ST_REV
81
r
[0]
Indicates the revision level of static data.
STRATEGY
83
S
r/w
ALL
[0]
This parameter is used to group blocks for their faster analysis.
Blocks are grouped by entering the same value in the STRATEGY parameter of each block.
TAG_DESC
82
S
r/w
ALL
[32 characters]
Used to enter a user-selected text to identify and assign blocks.
TARGET_MODE
85
S
r/w
ALL
[8] = AUTO (automatic)
16 = MAN (manual)
128 = O/S (out of service)
Desired mode of operation
TOT_VALVE_TRAV_LIM
126
S
r/w
ALL
[1000000.0]
Limit value for the total valve travel (Code 24)
TOTAL_VALVE_TRAVEL
125
r
[0.0]
Totaled double valve travel (Code 23)
TRAVEL_LIMIT_LOW
127
S
r/w
ALL
[0.0 %]
Limitation of the travel/angle of rotation [% of working range PV_SCALE] (Code 10)
value; The characteristic is not adapted.
TRAVEL_LIMIT_UP
128
S
r/w
ALL
[100.0 %]
Limitation of the travel/angle of rotation [% of working range PV_SCALE] (Code 11) upwards to the entered
value; The characteristic is not adapted.
Summary of Contents for 3730-4
Page 2: ...2 EB 8384 4 EN...
Page 127: ......
Page 188: ...188 EB 8384 4 EN...
Page 189: ...EB 8384 4 EN 189...
Page 190: ...190 EB 8384 4 EN...
Page 191: ...EB 8384 4 EN 191...
Page 192: ...192 EB 8384 4 EN...
Page 193: ...EB 8384 4 EN 193...
Page 194: ...194 EB 8384 4 EN...
Page 195: ...EB 8384 4 EN 195...
Page 196: ...196 EB 8384 4 EN...
Page 197: ...EB 8384 4 EN 197...
Page 198: ...198 EB 8384 4 EN...
Page 199: ...EB 8384 4 EN 199...
Page 206: ...206 EB 8384 4 EN...
Page 207: ...EB 8384 4 EN 207...
Page 208: ...208 EB 8384 4 EN...
Page 209: ...EB 8384 4 EN 209...
Page 210: ...210 EB 8384 4 EN...
Page 211: ...EB 8384 4 EN 211...