5.3
Status alarm according to Profile 3.01
Fault/diagnostic alarm
Value (hex) Status alarm acc. to
Profile 3.01
Operational errors
Device not initialized
0x1C
BAD_OUT_OF_SERVICE
Solenoid valve active
0x80
GOOD_NON_SPECIFIC
Total travel exceeded
0xA4
GOOD_MAINT_REQ
Control loop error
0x4A
GOOD_MAINT_REQ
Zero point error
0xA4
GOOD_MAINT_REQ
Autocorrection
0x80
GOOD_NON_SPECIFIC
Fatal error
0x0C
BAD_DEVICE_FAILURE
No emergency mode
0xA4
GOOD_MAINT_REQ
Reference test aborted
0x80
GOOD_NON_SPECIFIC
Temperature < –40 °C
0x80
GOOD_NON_SPECIFIC
Temperature > 80 °C
0x80
GOOD_NON_SPECIFIC
Initialization errors
x > range
0x80
GOOD_NON_SPECIFIC
Delta x < range
0x80
GOOD_NON_SPECIFIC
Incorrect attachment (mechanics/pneumatics)
0x80
GOOD_NON_SPECIFIC
Initialization time exceeded
0x80
GOOD_NON_SPECIFIC
Initialization/solenoid valve
0x80
GOOD_NON_SPECIFIC
Transit time too short
0x80
GOOD_NON_SPECIFIC
Pin position
0x80
GOOD_NON_SPECIFIC
Initialization running
0x80
GOOD_NON_SPECIFIC
Hardware errors
x signal
0x0C
BAD_DEVICE_FAILURE
i/p converter
0x0C
BAD_DEVICE_FAILURE
Hardware
0x0C
BAD_DEVICE_FAILURE
Data memory
0xA4
GOOD_MAINT_REQ
KH 8384-4 EN
21
Measured value status and valve diagnostics
Summary of Contents for 3730-4