• 2712 (0x0A98) · Resets the bus address to the default value of 126. The positioner restarts after the
reset is performed. The bus address is not reset when the identification parameters are reset.
Note:
The bus address can only be reset using this command in firmware version K 1.11 and higher.
• 32768 (0x8000) · Resets the identification parameters
• 32769 (0x8001) · Resets the start-up and function block parameters as well as the status classifica-
tion. After performing a reset, the positioner needs to be re-initialized!
• 32770 (0x8002) · Resets the start-up parameters. After performing a reset, the positioner needs to
be re-initialized!
Identification parameters (without bus address, valve and actuator data) include:
• Physical Block: CONFIG_BINARY_INPUT_2
1)
, DEVICE_INSTAL_DATE, DEVICE_MESSAGE, DESCRIP-
TOR, IDENT_ LIMIT_SWITCHES
1)
, IDENT_NUMBER_SELECTOR, TAG_DESC, TEXT_INPUT 1…5
1)
• AO Function Block: TAG_DESC
• AO Transducer Block: ACTUATOR_MAN, ACTUATOR_SER_NUM, ADD_GEAR_ID, ADD_GEAR_
INST_DATE, ADD_ GEAR_MAN, ADD_GEAR_SER_NUM, DEVICE_CALIB_DATE, DEVICE_
CHARACT
1)
, DEVICE_ CONFIG_DATE, TAG_DESC VALVE_MAINT_DATE, VALVE_MAN,
VALVE_SER_NUM, VALVE_TYPE
• DI1/2 Function Block: TAG_DESC
• DI1/2 Transducer Block: SENSOR_ID, SENSOR_MAN, SENSOR_SER_NUM, TAG_DESC
Start-up parameters (status classification, analysis of condensed state (Code 36) include:
• Physical Block: COND_STATUS_DIAG, DIAG_EVENT_SWITCH, DIAG_EVENT_SWITCH_2
1)
,
FEATURE
Function block parameters include:
• Physical Block: ALERT_KEY, FACTORY_RESET, FEATURE_SELECT, LOCAL_OP_ENA, ST_REV,
STRATEGY, TARGET_MODE, WRITE_LOCKING
• AO Function Block: ALERT_KEY, BATCH, CHECK_BACK_OPT, FSAFE_TIME, FSAFE_TYPE,
FSAFE_VALUE, IN_CHANNEL, INCREASE_CLOSE, OUT_CHANNEL, OUT_SCALE, PV_SCALE,
SIMULATE, ST_REV, STRATEGY, TARGET_MODE
• AO Transducer Block: ACTUATOR_ACTION, ALERT_KEY, CHARACT_TYPE
1)
, SELF_CALIB_CMD,
SELF_CALIB_STATUS, ST_REV, STRATEGY, TARGET_MODE
• DI1/2 Function Block: ALERT_KEY, BATCH, CHANNEL, FSAFE_TYPE, FSAFE_VAL_D, INVERT,
SIMULATE, ST_REV, STRATEGY, TARGET_MODE
• DI1/2 Transducer Block: ALERT_KEY, SENSOR_WIRE_CHECK, ST_REV, STRATEGY, TARGET_MODE
1)
Manufacturer-specific parameter
KH 8384-4 EN
43
Physical Block, Slot 0 ·
Profile-specific parameters
Summary of Contents for 3730-4