FEATURE_SELECT (64)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Coded bitwise, therefore more than one alarm possible at one time
Bit: 0 = false · 1 = true
Byte
Bit
Description
0
0
BAD_DEVICE_FAILURE sets DIAG_EXT-Bit · By using the 'Condensed status and di-
agnostic messages' profile extension, the DIAG.ext bit (Octet 1) is set when a fault
or the corresponding diagnostic alarm DIA_MAINTENANCE_ALARM is detected by
the positioner.
According to Profile 3.01, the DIAG.ext bit is set when one of the following errors is
detected by the positioner: Test calculation, fatal error, program loading error, no
production calibration, hardware, i/p converter
0
1
Test function activated · The activation of this function allows errors to be simulated
in TROVIS-VIEW (Positioner (AO, TRD) folder (> Simulation) (firmware version
K 1.11 and higher)
0
2
LO and active diagnostic function activate GOOD_FUNCTION_CHECK · During a
diagnostic test, a BAD_FUNCTION_CHECK would be activated according to the
profile. This can be prevented by activating this additional function which activates
GOOD_FUNCTION_ CHECK (firmware version K 1.11 and higher)
0
3
Use DP standard diagnosis (6 bytes) · Select whether the positioner responds to a
GET_DIAG telegram with the full diagnosis (14 using as Profile or 26 as manufac-
turer specification) or only with 6 bytes for DP standard diagnosis (firmware version
K 1.11 or higher)
FST_E_1 (148) to FST_E_4 (151)
Storage class: – · Read capability (r)
Tests MAN: Full stroke test (FST) – Setpoint deviation data set 1 to 4
• FST_E_1: Data set 1 (measured points 1 to 25)
• FST_E_2: Data set 2 (measured points 26 to 50)
• FST_E_3: Data set 3 (measured points 51 to 75)
• FST_E_4: Data set 4 (measured points 76 to 100)
FST_SS_1 (146) and FST_SS_2 (147)
Storage class: – · Read capability (r)
Tests MAN: Full stroke test (FST) – Drive signal data set 1 and 2
• FST_SS_1: Data set 1 (measured points 1 to 50)
• FST_SS_2: Data set 2 (measured points 51 to 100)
54