Hardware errors
Error codes – Recommended action
Condensed state alarm active, when prompted,
ERR
appears.
When fault alarms exist, they are displayed here.
62 x signal
Additional indication at the fault
alarm contact!
– Measured data recording for actuator has failed.
– Conductive plastic element is defective.
The emergency mode on the display is indicated by a blinking
closed-loop operation icon and 4 dashes instead of the position
indication.
Open-loop operation:
If the measuring system has failed, the positioner is still in a reli-
able state. The positioner switches to emergency mode where the
position cannot be accurately controlled anymore. However, the
positioner continues operation according to its reference variable
signal so that the process remains in a safe state.
Status classification [Maintenance required]
Recommended action – Return the positioner to SAMSON AG for repair.
63 SIL shutdown/w too small
1)
Emergency shutdown of the i/p block is implemented by
3.8 mA or 4.4 mA (depending on the positioner version)
2)
The set point w is smaller than 3.7 mA.
This state is indicated on the positioner display by a
blinking
LOW
Status classification [No message]
Recommended action Re. 1) Raise the current (depending on version) above the limit.
Re. 2) Check set point.
If necessary, limit the current source downwards so that
no values below 3.7 mA can be issued.
64 i/p converter
– The circuit of the i/p converter has been interrupted.
Status classification Failure (status classification change not possible)
Recommended action – Return the positioner to SAMSON AG for repair.
EB 8384-6 EN
105
Code list
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...