Configuration enabled
Default:
No
Turn
®
Code 3
, display:
No
Press
, Code 3 blinks
Turn
®
YES
Press
, display
Limiting the signal pressure:
Pressure limit
Default:
No
Turn
®
Code 16
Press
, Code 16 blinks
Turn
until the required pressure limit ap-
pears.
Press
to confirm the pressure limit setting.
7.5
Checking the operating
range of the positioner
To check the mechanical attachment and the
proper functioning, the valve should be
moved through the operating range of the
positioner in the
manual operating mode
with the manual set point.
Selecting
manual operating mode:
Operating mode
Default
MAN
Turn
®
Code 0
Press
, Code 0 blinks
Turn
®
MAN
Press
. The positioner changes to the
manual operating mode .
Checking the operating range:
Manual set point
(current angle of rotation is
indicated)
Turn
®
Code 1
Press
, Code 1 and
blink
Turn
until the pressure in the positioner
builds up, and the control valve moves to its
final positions so that the travel/angle of ro-
tation can be checked.
The angle of rotation of the lever on the
back of the positioner is indicated. A hori-
zontal lever (mid position) is equal to 0°.
To ensure the positioner is working prop-
erly,
the outer bar elements may not blink
while the valve is moving through the oper-
ating range.
Exit
Code 1
by pressing the rotary
pushbutton ( ).
58
EB 8384-6 EN
Start-up – Settings
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...