positions and adopts it as the operating
range with limits of lower travel/angle
range value (
Code 8
) and upper travel/an-
gle range value (
Code 9
).
Enable configuration:
Note:
If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Enable configuration
Default
No
Turn
®
Code
3
, display:
No
Press
, Code 3 blinks
Turn
®
YES
Press
, display
Enter the pin position:
Pin position
Default
No
Turn
®
Code 4
Press
, Code 4 blinks
Turn
®
Pin position on lever (see relevant
section on attachment)
Press
Turn
®
Skip nominal range (Code 5)
and go to Code 6.
Select the initialization mode:
Initialization mode
Default
MAX
Turn
®
Code 6
Press
, Code 6 blinks
Turn
®
MAN
Press
to confirm the
MAN
as the initial-
ization mode.
Enter OPEN position:
Manual set point
(the current angle of rotation
is displayed)
Turn
®
Code 0
Press
, Code 0 blinks
Turn
®
MAN
Press
Turn
®
Code 1
Press
, Code 1 blinks
Turn
clockwise in small steps until the re-
quired valve position is reached. The valve
must be moved with a monotonically in-
creasing signal pressure.
Press
to confirm the OPEN position.
Start initialization:
4
Press INIT key to start initialization!
EB 8384-6 EN
63
Start-up – Settings
mm
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...